Installation:
This Lifelight Pro Cylindrical Surface Mount Emergency Luminaire can be installed on solid or T-BAR
ceilings or used to replace an existing unit.
•
Locate the installation position.
•
Refer Images and Dimensions below for the Cut-out Hole and other dimensions.
•
Pre-drill mounting holes.
•
Mount base plate and use suitable fixings to secure the base plate into the pilot holes.
•
Bring in supply cables via the rear entry hole.
•
Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings
terminate the DALI or DATA cable to the terminals marked Da Da or DATA).
•
Install the cylindrical top cover, containing the control gear, ensuring to reconnect the control gear
assembly to the connector from the supply terminal block.
•
Ensure the Battery is connected.
•
Screw the cover to the base plate.
•
For HIVE version please install provided antenna on the side.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
Networking:
When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert
the relevant Smart Node PCA.
Images and Dimensions:
Testing:
When the Lifelight Pro Cylindrical Surface Mount Emergency Luminaire unit is connected to the un-
switched active, it must be allowed to charge the battery for at least 24 hours. The emergency lamp only
illuminates during a power fail. Conduct the following tests:
•
The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer
to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.