Installation:

 

 

This LBS2N Surface mount non-maintained Emergency Luminaire can be installed on solid surface or 

used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes 

 

Mount base and use suitable fixings to secure the base into the pilot holes 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 

conduit entry) 

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Ensure the Battery is connected. 

 

Install the top cover, containing the LED head, ensuring to reconnect the control gear assembly to 

the LED head. 

 

Screw the cover to the base. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

 

 

 

Images and Dimensions:

 

 

 

 

 

 

 

Initial Testing:

 

 

When the LBS2N unit is connected to the un-switched active, it must be allowed to charge the battery 

for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the following 

tests: 

 

 

During the first commissioning test the emergency lamp must illuminate for at least 2 hours after 

disconnection from the main supply. The results of all tests are required to be recorded in a service 

logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, 

remedial action must be taken to repair the situation and once completed, the unit must pass a 

subsequent test.  

 

 

Press and hold Test Button for each LED head or switch Off Mains Supply, check that the 

emergency lamps are On. 

 

 

Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:   The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 

to spacing tables for installation positions):

 

 

 

Refer to the Technical Label on the fitting for classification information. 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 

performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-

life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 