1945026
V1.3
16 March 2022
Instruction Sheet Template - V1.3
–
Updated 20/01/2022
Installation:
This ELIFE-X-LI Recessed Non-maintained Emergency can be installed on PLASTER or T-BAR ceilings
or used to replace an existing unit.
•
First plan the assembly layout ensuring the Control gear is kept away from any heat source.
•
Refer Images and Dimensions below for the Cut-out Hole and other dimensions.
•
Insert the control gear through the mounting hole and secure.
•
Connect the power cord to the power supply.
•
Use the Spring Clip Mount to mount the Head to the ceiling.
•
Please ensure the control pack is suspended above the ceiling. If the control pack is to be mounted
or placed on top of the ceiling then please ensure the ceiling is capable of supporting it in
compliance with the relevant regulations with respect to mounting above/on the ceiling.
Dimensions:
Head depth:
40mm including connector
Head:
95mm diameter (with adaptor ring 145mm)
Cut-out Hole:
Recommended 85mm diameter (Will suit 70mm-135 mm with adaptor ring)
Control gear:
232mm (L) x 51mm (W) x 42mm (H)
Testing:
•
When the Lifelight unit is connected to the un-switched active, it must be allowed to charge the
battery for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the
following tests:
•
The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1(refer to
spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.