Images and Dimensions
Installation:
The Economy Lithium Cleverfit LED Exit (ECFLED-LI) can be installed either Ceiling or Wall Mounted and
can be mounted perpendicular to a wall using the (optional) Cleverfit Cantilever Bracket. The ECFLED uses
a “slide connect bracket base” that is mounted and wired into position first. The main body can be installed
once the base is wired or later to avoid damage during the construction phase. Please follow the steps
below to install the Cleverfit Exit:
•
Disengage the slide connect bracket from the exit body. Position the base in the mounting position.
•
Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the
bracket using appropriate fixings (not supplied).
•
Connect the 240VAC supply to the mounting bracket.
•
Configure all the mounting parts and cable entry points as below (if required) and engage the body into
the slide connect bracket. Apply mains power and check that the Cleverfit Exit is operational.
Cleverfit Maintenance:
Lamp Replacement:
•
Use only the lamp(s) recommended on the label inside the Cleverfit.
•
To replace the lamp bar, remove the self-tapping screws, disconnect the signal cable and install
the new lamp bar.
•
*Please note that the 50,000 hour LED Lamp Bar used in the Cleverfit Exit does not suffer from burn
out. Lamp replacement can be done as scheduled maintenance, at >5 year intervals. Please make a
note, in the site logbook, as to when lamps should be changed.
Battery Replacement:
•
Use only the battery recommended on the label inside the Cleverfit and on this instruction.
•
Remove the screw securing the fitting to the mounting bracket.
•
Remove the fitting from the bracket by sliding it forward.
•
The battery is located in the top of the fitting. See images.
•
Remove the clip holding the battery.
•
Unplug the battery from the PCA and remove it.
•
Insert the new battery into the holder, route the DC cable to the PCA and plug the new battery
into the connector.
•
Secure the battery using clip.
Changing Exit Legend Inserts:
The Cleverfit Exit uses Clevertronics patented “Tamper proof” Exit legend cover and comes
complete with spare legend inserts to enable straight on, left or right arrow as well as SS/DS
combinations.
To change an Exit legend insert first remove the diffuser. The clear tamper proof cover is held in
place by 3 locking tabs in the top inside area of the diffuser. Use a tool to disengage and push
the locking tabs through to release the cover and remove the insert, replacing it with the desired
one. When double sided is required remove the cardboard insert from the second side when
adding decal.
To re-install the clear cover, first engage the 3 small lugs on the bottom of the cover into their
respective recesses in the diffuser. Once sure the lugs are located, and then the 2 side lugs,
carefully push the 3 locking tabs back in, to complete the process.
Cable Entry Point
– Top of
bracket for ceiling mount,
20mm diameter, located in
centre of bracket.
Mounting Bracket - front view
Wall Mount screw
fixing point
Wall Mount screw
fixing point
Cable Entry Point
–
Rear of bracket for wall mount, 20mm
diameter, located in centre of bracket. Note: Bracket shown
from front with the terminal block cover removed.
Mounting Bracket
–
top view
Cable Entry Point
–
Rear of bracket for wall mount, 20mm
diameter, located in centre of bracket Note: Bracket only
shown from front with the terminal block cover removed.
Ceiling mount -
screw fixing points.
(Same other side)
250
Battery PCA
Fitting Top View