Installation: 

The product can be mounted/suspended from any solid surface. Follow the below installation steps: 

 

Determine the installation and power entry method. 

 

Undo the Diffuser Clips, remove the Diffuser and Gear Tray. Position the batten base in the desired 

location and Mark out the fixing points on the mounting surface. 

 

If the cable entry is to be via the rear of the body – Drill out a suitable entry-hole in the rear of the 

batten body (must be suitably sealed after cable entry using a sealant).  If the cable entry is via the 

end of the batten - Install the provided cable gland, or bring in conduit, to the base as required for 

the intended power access.  

Note: Only round cables are to be used with the cable gland for an IP65 seal. Keep cable entry 

straight and tension free.  Ensure all seals are tight.  

min. wire diameter 6mm, max. 12mm. 

 

For surface mounting -

, there are 3 extrusions/posts at each end of the base. Drill out the desired 

number of fixing points at each end. 

Fixings must only be through the extrusions/mounting 

posts. 

o

  Position the fitting to the mounting surface and mark the mounting holes. 

o

  Cable/Gland entry to be down if mounting vertically. 

o

  Drill the mounting holes. 

o

  Fix the base to the surface with appropriate fixings. 

o

  Seal any penetrations/fixing points with appropriate sealant. 

 

For Surface Mount Clip

 

mounting, 

measure/mark spacing (see Dimensions image),

 

install 

stainless steel clips to surface (use appropriate fixings), then snap batten into clips. 

 

For Suspension Mounting, 

measure/mark spacing (see Dimensions image),

 

install suspension 

device, E.G chain, and connect chain to batten base. 

 

Wire mains power cable, 240V 50Hz, to terminals marked Lsw (Switched Active), Lem 
(Emergency/Unswitched Active), N & 

 (and DALI Cables to terminals Da Da as applicable) 

 

Set Colour Switch to the desired colour (3000K / 4000K / 5700K, 4000K set as default) 

 

Attach Gear Tray to lanyards. 

 

Re-Install the Diffuser, close all the Diffuser Clips and secure with screws 

 

Wiring: 

 

NOTE: Refer to Microwave Sensor Supplement for wiring -SEN Products 

 

Colour Setting:

 

 

 

Dimensions: 

 

 

 

Battery Replacement (non-POD) 

1.  Prior to any work, isolate power to any Batten that requires battery replacement 

2.  Open the Diffuser by releasing the Batten Diffuser Clips  

3.  Remove Gear Tray by unclipping the Gear Tray Clips on each side (ensure the Gear Tray is 

supported while unlocking clips) 

4.  Remove Battery connector from the Emergency Driver 

5.  Remove Battery by removing the Screw/Washer/Nuts 

6.  Install replacement Battery/Screw/Washer/Nuts and connect into Emergency Driver 

7.  Re-Install the Gear Tray onto the Gear Tray Clips 

8.  Re-Install the Diffuser, close all the Diffuser Clips and secure with screws 

NOTE: For POD products refer to Instruction Sheet for LP POD’s provided with product  

 

Testing Procedure:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 

hours. Conduct the following tests: 

 

The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the 

unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation 

and once completed, the unit must pass a subsequent test.  

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:   The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

 