SEQUENCE OF OPERATIONS

Steam Coil Boiler Base

1. To turn the unit on, depress the red on/off rocker switch.

x

115 VAC is sent to the upper cabinets and terminal block in control box.

x

115 VAC is sent to normally open drain valve closing it.

x

115 VAC is sent to L1 and L2 of the water level board.

2. With the water level board energized and no water in the boiler 

x

115 VAC is sent from the WF terminal to the fill solenoid.

x

The fill solenoid opens and the boiler fills through the drain valve.

x

The water fills to the low probe shorting it to ground

x

115 VAC is sent from the HTR terminal through the normally closed contacts of the
highlimit pressure switch to contacts of the ice cube relay and the amber reset switch,
energizing the amber light.

3. When the momentary amber switch is depressed 115 VAC is sent to the coil of the ice cube

relay closing it.

x

The relay latches itself through a jumper to the coil.

x

If either the high-pressure switch or the low water cut off float switch opens, the
latch circuit opens.

x

When the contacts close the amber light will energize and the process may begin
again.

x

The relay contacts close sending 115 VAC through the normally closed contacts of the
operating pressure switch to the coil of the supply steam solenoid. .

4. With 115 VAC to the coil of the supply steam solenoid.

x

The solenoid opens.

x

Steam is sent to the coil in the boiler.

5. The water in the boiler is heated to steam. 

x

As steam is generated and pressure builds the air is pushed out through the steamtrap.

x

When steam goes through the steam trap and heats it to 192 degrees it closes.

6. Pressure builds in the boiler to the set point .

x

The operating pressure switch opens and the heat circuit is de-energized.

x

When the pressure drops below the set point the heat circuit is energized and the heat
process begins again.

7. Water continues to fill until the high probe is grounded.

x

When the high probe is grounded the WF terminal on the water level board is de-
energized.

x

The fill solenoid closes until the high probe is ungrounded for 05 seconds.

Summary of Contents for 24CSM Series

Page 1: ...technical and technological changes revisions or updates Cleveland Range LLC assumes no liability or responsibility regarding errata changes revisions or updates Qualified Cleveland Range LLC Authoriz...

Page 2: ...Cleveland Range LLC 1333 East 179th St Cleveland Ohio U S A 44110 Ph 1 216 481 4900 Fx 1 216 481 3782 Visit our Web Site at www clevelandrange com...

Page 3: ...ther the high pressure switch or the low water cut off float switch opens the latch circuit opens x When the contacts close the amber light will energize and the process may begin again x The relay co...

Page 4: ...the unit is turned off by depressing the red rocker switch x 115 VAC is removed from the heat circuit x 115 VAC is removed from the drain circuit and the normally open drain valve opens allowing the u...

Page 5: ......

Page 6: ...contact of the high pressure switch to the amber reset switch energizing the amber light 3 When the momentary amber switch is depressed 115 VAC is sent to the ice cube relay closing it x The relay la...

Page 7: ...seconds the WF terminal is energized and the water fill circuit begins again 8 When the unit is turned off by depressing the red rocker switch x 115 VAC is removed from the heat circuit x 115 VAC is r...

Page 8: ......

Page 9: ...ressed Yes No No Yes No Replace the high limit pressure switch With the SLWCO switch temporarily bypassed does the Amber light go off with the reset switch depressed No Yes Yes Replace the SLWCO switc...

Page 10: ...s water leaving the fill solenoid Replace wiring to drain solenoid Does the steamer have the optional intermittent blowdown timer Replace the wiring to the intermittent blowdown timer Is there 120 VAC...

Page 11: ...PROBLEM Steam Coil Boiler Stops Producing Steam Boiler stops steaming Does the amber light in the reset switch come on Is the temperature sensitive dot surrounded by a yellow circle on the water board...

Page 12: ...eplace the fill solenoid With a jumper across terminals HI and C on the waterboard is there 120 VAC between L2 and WF Replace the water board Yes The probe circuit is open Check continuity of the prob...

Reviews: