User Manual : ZGAS
CLEODE
page
19
sur
21
IV.2.2.5
Cluster IAS Zone
This cluster is used to report the value of the attribute
ZoneStatus
when the sensor has detected smoke or carbon
monoxide. Upon detection and end of detection, a command of type
ZoneStatusChangeNotification
is sent in the
network to indicate the new value of
ZoneStatus
.
Attributes
Attributes identifier
ZoneState
0x0000
ZoneType
0x0001
ZoneStatus
0x0002
IAS_CIE_Address
0x0010
The sensor performs an Enrolment request with the CIE (Control and Indicating Equipment) automatically after
writing the IEEE address of CIE in the attribute
IAS_CIE_Address.
The
ZoneStatus
attribute is a bitmap. The description of each bit is shown in the following table:
Bit
Description
Values
0
Monoxide Alarm
1 – Alarmed
0 – Not Alarmed
1
Smoke Alarm
1 – Alarmed
0 – Not Alarmed
2
Tamper
1 – Tampered
0 – Not Tampered
3
Battery
1 – Low battery
0 – Battery OK
4
Supervision reports
1 – Reports
0 – Does not reports
5
Restore reports
1 – Reports restore
0 – Does not reports restore
6
Trouble
1 – Trouble/failure
0 – OK
7
AC (mains)
1 – AC/Mains fault
0 – AC/Mains OK
8
Test
1 – Sensor is in test mode
0 – Sensor is in operation mode
9
Battery defect
1 – Sensor detects a defective battery
0 – Sensor battery is functioning battery
10-15
Reserved
Reserved
IV.2.2.6
Cluster Warning Device
This cluster is used to start a fire sound at the request of CIE of the time defined in the attributes MaxDuration.
Attributes
Attributes identifier
MaxDuration
0x0000