![CleaverBrooks 4WI Operation, Service And Parts Manual Download Page 71](http://html1.mh-extra.com/html/cleaverbrooks/4wi/4wi_operation-service-and-parts-manual_2622058071.webp)
750-211 (revised 2009)
Promethean Boilers, Model 4WI Manual
5-1
CHAPTER 5
Starting and Operating
Instructions
5.1 — General Preparation for Startup: All Fuels
Instructions in this chapter are based upon installation being complete and all electrical, fuel, water, and vent stack
connections are made.
The operator should be familiar with the burner, boiler, and all controls and components. To quickly locate and
identify the various controls and components mentioned in this chapter, refer to the illustrations and the contents
of Chapters 1, 2, and 3. Instructions for adjusting major components are given in Chapter 6, and these instructions
should be reviewed prior to firing. The wiring diagram should also have been studied, along with the firing
sequence outlined in Chapter 4.
Verify supply of fuel and proper voltage. Check for blown fuses, open circuit breakers, dropped out overloads, etc.
Check reset of all starters and controls having manual reset features. Check the lockout switch on the programmer
and reset if necessary.
The boiler should be filled with water to the proper operating level using water of ambient temperature. Be sure
that treated feedwater is available and used. In heating applications, the entire system should be filled and vented.
It is recommended that the starting instructions be read completely until they are thoroughly understood before
attempting to operate the boiler, rather than performing each operation as it is read for the first time. Failure to follow
these instructions could result in serious injury or death.
Prior to firing a boiler, be sure that discharge piping from safety valves or relief valves, and discharge piping from all
blowdown and drain valves, is piped to a safe point of discharge, so that emission of hot water or steam cannot possi-
bly cause injury. Failure to follow these instructions could result in serious injury or death.
!
Warning
!
Warning
Summary of Contents for 4WI
Page 46: ...Burner Operation and Control 2 22 750 211 revised 2009 Promethean Boilers Model 4WI Manual...
Page 62: ...Waterside Care and Requirements 3 16 750 211 revised 2009 Promethean Boilers Model 4WI Manual...
Page 70: ...Sequence of Operation 4 8 750 211 revised 2009 Promethean Boilers Model 4WI Manual...
Page 114: ...Adjustment Procedures 6 28 750 211 revised 2009 Promethean Boilers Model 4WI Manual...