30
Resetting the burner from restricted lock out:
NOTICE:
If the control locks out three times
before a call for heat is satisfied, it will enter
restricted lockout mode in order to limit the
amount of unburned oil in the combustion
chamber.
(1) Push the reset button in for 15 seconds.
Release the reset button when the red
light turns off and the yellow light
turns
on.
Figure 26: Oil Primary Control Reset Button
SETTING THE DRAFT
(1) Allow the furnace to run for 5 to 10 minutes.
(2) Refer to Figure 27 to locate the draft gauge
hole.
(3) Insert a draft gauge through the hole in
the observation port. Follow the
manufacturers instructions for adjusting the
barometric damper to obtain -0.02” w.c. draft
over
fire.
(4) If a proper draft is not obtained, follow the
instructions below to check for a vacuum in
your
building.
Checking for vacuum in your building:
(1) Have someone slowly open an overhead
door while you are taking a draft reading.
(2) Watch the draft gauge and tell them to stop
when you get a -0.02” w.c. draft over fire.
(3) Measure the opening created by the
overhead door. This is the opening size you
need for make up air to allow the furnace to
draft
properly.
Figure 27: Draft Gauge Hole in the
Observation Port
WARNING:
Do not operate you furnace
if a proper draft is not obtained or damage
to critical burner components will occur.
RESETTING THE OIL PRIMARY CONTROL
CE70043
PRIMARY CONTROL
RESET BUTTON
CE70173
DRAFT
GAUGE
HOLE
Summary of Contents for CE-140
Page 50: ...50 NOZZLE ADAPTER HEATER BLOCK ASSEMBLY 2 3 19 5 7 8 15 9 17 14 18 16 13 1 4 6 10 11 12 ...
Page 52: ...52 MANIFOLD BLOCK ASSEMBLY 8 6 2 1 4 17 3 9 5 7 12 13 14 15 16 18 19 11 10 ...
Page 58: ...58 3 4 6 1 2 5 CE 140 180 BLOWER ...
Page 62: ...62 2 3 4 5 6 1 CE 250 BLOWER ...
Page 66: ...66 CE 330 BLOWER 12 8 7 4 13 1 2 3 5 6 9 10 11 ...
Page 70: ...70 CE 440 BLOWER 12 8 7 4 13 1 2 3 5 6 9 10 11 ...