41000981 Iss 09

 

MODEL 

This  unit  is  a  1035mm  6  or  9kW  air  curtain  heater 
designed for mounting above entrances but may also be 
used  as  a  space  heater.    It  is  supplied  complete  with 
remote mounting control box. 
 

MOUNTING 

When  mounted  over  a  standard  shop  doorway  the  unit 
should  be  fitted  as  low  as  possible  and  not  more  than 
2.3 meters from ground level.  A single unit will provide 
reasonable  coverage  for  a  one  metre  doorway,  and  for 
wider doorways units can be mounted end to end. 
 
The  unit should  be positioned so that the airflow is not 
obstructed by any part of the doorframe. When installed 
the  top  of  the  heater  case  should  be  a  minimum  of 
200mm from the ceiling. 

 

 
 

                                   

880 

 
 
 
 
 

         

75            

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION

 

Carefully  unpack  the  unit  and  remove  the  top  cover 
fixing  screws.    The  heater  may  be  mounted  using  the 
mounting bracket provided. 
 
Loosen mounting screws, allowing the mounting bracket 
to  be  removed  from  the  unit.    Making  sure  that  the 
mounting  bracket  is  horizontal,  fix  the  bracket  to  the 
wall using 4 x No 8 wood screws. 
 

Place  the  unit  on  the  mounting  bracket  ensuring  the 
washers  are  spaced  as  shown  on  Fig  2  (a  plain  washer 
either side of the mounting bracket). 
 
Tighten screws to hold the unit at the required angle. 
 

 

 

Fig 2 

WALL BRACKET ASSEMBLY 

 
The  heater  may  also  be  mounted  directly  onto  a 
suitable  wall  or  bearer  by  four  No.  8  wood  screws 
through  the  holes  provided  in  the  back  of  the  unit 
casing.    Keyhole  slots  are  provided  for  the  top  two 
fixings (fig 1). 
 

ELECTRICAL CONNECTIONS 

The  heater  is  suitable  for  connection  to  a  400-415  volt 
3 phase  50Hz  supply.    With  modification  the  unit  can 
also be on a 230-240 volt 50Hz supply.  For 230-240 volt 
single  phase  operation,  link  terminals  L1,  L2  and  L3  on 
the main input terminal block and connect the supply to 
L.  The heater consumes approximately 6 or 9kW on the 
full heat setting.  The connections to be made between 
the heater and the remote control box are shown in Fig 
3 (see back page).  An earth terminal is adjacent to the 
terminal block and is clearly marked with the symbol   .  
For  safety  reasons  a  good  earth  connection  must 
ALWAYS be made to the heater and control box. 
 
The  unit  must  be  wired  in  accordance  with  IEE 
regulations for the Electrical Equipment of Buildings and 
the  installer  should  ensure  that  a  suitable  fused 
isolating switch is connected in the mains supply. 

 

 

REMOTE CONTROL BOX CONNECTIONS 

 

 

 

CONTROLS 

The  unit  is  designed  to  provide  2  levels  of  heat,  4.5kW 
and  9kW  for  HE7433,  3kW  and  6kW  for  HE8326  together 
with  2  fan  speeds,  normal  and  boost.    The  remote 
control  box  houses  4  single  pole  switches  to  give  the 
following functions: 
 
 
SWITCH 1 (left-hand) 

 

ON/OFF 

SWITCH 2 

 

 

FAN SPEED CONTROL 

SWITCH 3 

 

 

½ HEAT ON/OFF 

SWITCH 4 

 

 

½ HEAT ON/OFF 

 

FRONT VIEW 

 

 

 

 

 

 

MAINTENANCE 

ALWAYS ENSURE THAT THE MAIN EXTERNAL ELECTRICITY 
SUPPLY  IS  SWITCHED  OFF  BEFORE  SERVICING  OF  THIS 
SCREEN-ZONE HEATER. 
 
To obtain the best results from the heater it is essential 
to avoid the accumulation of dust and dirt within the 
unit and on the inlet and discharge grilles.  Regular 
cleaning is necessary with particular attention to the 
fronts and backs of the fan motor blades.  Cleaning of 
the fan is best carried out with a soft brush. 
 

THERMAL CUT-OUT 

The units are protected from overheating in the event of 
fan failure or an obstruction of the free airflow, by thermal 
cut outs.  If this happens the thermal cut outs effectively 
switch off the appliance. The appliance will not operate 
until the thermal cut outs are manually re-set.  This should 
be done by a competent electrician. 

 

 

TO REPLACE A SWITCH IN THE CONTROL BOX 

a)

 

Switch off the mains supply 

b)

 

Remove the switch box cover. 

c)

 

Disconnect the wiring to the switch. 

d)

 

Release the spring clips and push out the switch. 

e)

 

Fit the replacement switch, reconnect the wiring and 

replace the cover. 

 

SPARES 

It is essential when ordering spares or replacement parts 
to  state  the  model  number  HE7433  and  the  serial 
number on the rating place fixed to the top of the unit. 
 
NB:    DO  NOT  COVER  ANY  OF  THE  AIR  INLET  OR  OUTLET 
GRILLES AT ANY TIME. 
 
In  the  interest  of  progress  the  Company  reserves  the 
right  to  vary  specifications  from  time  to  time  without 
notice.    The  material  listed  is  offered  subject  to  the 
Company’s  General  Conditions  of  Sale,  a  copy  of  which 
can be obtained on request. 
 

 

 

Fig 1

 

OUTLINE DRAWING 