MODEL 

This  unit  is  a  6kW  commercial  heater  designed  for 
mounting on the wall to be used as a space heater.  It is 
supplied complete with remote mounting control box. 
 

MOUNTING 

The unit should be fitted between 2.5 to 3 meters from 
ground level. The angle of the heater can be adjusted in 
steps, 45 deg. vertically and 180 deg. horizontally.  
 
The  unit should  be positioned so that the airflow is not 
obstructed.  When  installed  the  top  of  the  heater  case 
should be a minimum of 200mm from the ceiling. Never 
install heaters opposite to each other.  

 

 

 
 
 
 
 

INSTALLATION

 

The  wall  bracket  is  secured  to  one  of  the  inner 
cardboard box corners. Cut the plastic bag to remove it. 
All fixing screws, switch and parts for the swivel bracket 
are  packed  under  the  terminal  cover.  Carefully  unpack 
the unit and remove the terminal cover. 
 
NOTE: 

The heater must always be installed 

horizontally

, using the mounting bracket provided. This 

ensures correct positioning and adequate clearance. 
 
Assemble the swivel bracket as shown on Fig.2. Use  M8 
and M5 bolts with locknuts and washers as supplied in a 
bag. Attach the assembled bracket to the bottom of the 
heater  by  using  4  x  M6  bolts  with  plain  and  spring 
washers as shown on the Fig.3. 

 

 

Fig 2 

SWIVEL BRACKET ASSEMBLY 

 

 

 

Fig 3 

SWIVEL BRACKET ASSEMBLY 

 
Secure the wall bracket to the wall with suitable 
fixings. Ensure the position of this bracket will allow 
suitable clearances between the heater, when fitted, 
and adjacent walls. Minimum of 

3 fixings

 

must be used

 

to secure the wall bracket to the wall. The weight of 
the heater is 

11.5kg 

 
Attach the heater to the wall bracket. 
 
Finally adjust the direction of the heater to the desired 
area and tighten up all clamping nuts and bolts. 
 

ELECTRICAL CONNECTIONS 

The  heater  is  suitable  for  connection  to  230-240  Volts 
single phase  50Hz  supply.  The  heater  consumes 
approximately  6kW  on  the  full  heat  setting.    The 
connections  to  be  made  between  the  heater  and  the 
remote  control  box  are  shown  in  section  ‘CONTROLS’.  
Earth  terminals  are  adjacent  to  the  terminal  block  and 
are  clearly  marked  with  the  EARTH  symbol.  For  safety 
reasons a good earth connection must ALWAYS be made 
to the heater and control box. 
 
The  unit  must  be  wired  in  accordance  with  IEE 
regulations for the Electrical Equipment of Buildings and 
the  installer  should  ensure  that  a  suitable  fused 
isolating switch is connected in the mains supply. 

 

 

REMOTE CONTROL SWITCH CONNECTIONS 

 

MAINTENANCE 

 

H1 – 

HEAT1 3kW

,  H2 – 

HEAT2 3kW

,  F – 

FAN

 

N – 

NEUTRAL

,  L – 

SPARE TERMINAL

, E - 

EARTH

  

 

CONTROLS 

 
The unit is designed to provide 2 levels of heat; 
3kW-6kW together with fan only for air circulation.  The 
remote control box houses 3 double pole switches to give 
the following functions: 
 
SWITCH 1 (left-hand) 

ON/OFF / FAN ONLY 

SWITCH 2 

 

HEAT I. 

SWITCH 2+ SWITCH 3 

HEAT II. 

 

FRONT VIEW 

     
 
 
 
 
 
 
 
 
 
 

One control unit can control only 1 heater. 

 

For more details please see wiring diagram.

 

ALWAYS ENSURE THAT THE MAIN EXTERNAL ELECTRICITY 
SUPPLY  IS  SWITCHED  OFF  BEFORE  SERVICING  OF  THIS 
HEATER. 
 
To obtain the best results from the heater it is essential 
to avoid the accumulation of dust and dirt within the 
unit and on the inlet and discharge grilles.  Regular 
cleaning is necessary with particular attention to the 
fronts and backs of the fan motor blades.  Cleaning of 
the fan is best carried out with a soft brush. 
 

THERMAL CUT-OUT 

The units are protected from overheating in the event of 
fan failure or an obstruction of the free airflow, by two 
thermal cut outs.  If this happens the thermal cut outs 
effectively switch off the appliance. The appliance will not 
operate until the thermal cut outs are manually re-set.  
This should be done by a competent electrician. 

 

RESETING THERMAL CUT-OUT 

The cut-outs are located under the top cover on the top 
of the heating element. 
 
a) To reset the cut-out, allow the appliance to cool for 
20 minutes.  
 
b) Gently press the plastic square button on the top of 
the cut-out. 
 
c) Restart, switch ON the appliance. 

 

 

TO REPLACE A SWITCH IN THE CONTROL BOX 

a)

 

Switch off the mains supply 

b)

 

Remove the switch box cover. 

c)

 

Disconnect the wiring to the switch. 

d)

 

Remove the retaining screw and push out the switch. 

e)

 

Fit the replacement switch, reconnect the wiring and 

replace the cover. 

 

SPARES 

It is essential when ordering spares or replacement parts 
to  state  the  model  number  CH06CS  and  the  serial 
number on the rating place fixed to the top of the unit. 
 
NB:    DO  NOT  COVER  ANY  OF  THE  AIR  INLET  OR  OUTLET 
GRILLES AT ANY TIME. 
 
In  the  interest  of  progress  the  Company  reserves  the 
right  to  vary  specifications  from  time  to  time  without 
notice.    The  material  listed  is  offered  subject  to  the 
Company’s  General  Conditions  of  Sale,  a  copy  of  which 
can be obtained on request. 
 

 

 