2. Installation & Connection Details 

Fig. 1: CH06CSi/CPi Dimensions 

Fig. 2: CH09i/12i/15i Dimensions 

2.1  Mounting 

 

Ensure that the heater is fixed on a secure wall, 

within  the  mounting  height  limits  stated  in 

‘clearance  distances’.  Mount  the  heater  as 

shown in figures 1 and 2.  

 

The angle of the heater can be adjusted in steps, 

45 deg. vertically and 180 deg. horizontally.  

 

The weight of the CH06CSi/CPi models is 

11.5kg, and the weight of the CH09i/12i/15i 

models is 14kg.  

 

2.2  Electrical Connections  

 

(CH06CSi): 

The heater is suitable for connection 

to 230-240 Volts single phase 50Hz supply. The 

heater  consumes  approximately  6kW  on  the  full 

heat setting. The maximum current draw is 25A.  

 

(CH06CPi, CH09i/12i/15i): 

The heater is suitable 

for  connection  to  a  400-415  volt  3 phase  50Hz 

supply.    With  modification  the  CH06CPi  and 

CH09i/12i units can also be connected on a 230-

240 volt 50Hz supply.  

 

The maximum current draw for the 06CPi/09i/12i 

models are 25A, 37.5A and 50A for single phase, 

and  approximately  8.3A,  12.5A  and  16.6A  per 

phase for a three phase connection respectively.  

 

The maximum current draw for the CH15i model 

is approximately 20.8A per phase.  

 

For  230-240  volt  single  phase  operation,  link  

terminals  L1,  L2  and  L3  on  the  main  input      

terminal block and connect the supply to L.   

 

The heater consumes approximately 6kW, 9kW, 

12kW or 15kW (CH06CPi, CH09i/12i/15i models 

respectively) on the full heat setting.  

 

The connections to be made between the heater 

and  the  remote  control  box  are  shown  in  the  

section  ‘control  guide  and  connections’.  When 

controlling  more  than  one  heater  by  one         

controller, 

connections to the terminals 2, 3, 4 

& 5 must be connected via an isolator switch.

  

 

Earth terminals are adjacent to the terminal block 

and are clearly marked with the symbol      .  

 

For safety reasons a good earth connection must 

ALWAYS be made to the heater and control box. 

 

 

51000214 Iss 01 

Summary of Contents for CH06CPi

Page 1: ...rnton Industrial Estate Milford Haven Pembrokeshire SA73 2RT Tel 01646 692172 Fax 01646 695195 Mon to Thu 8 30am to 4 30pm Fri 8 30am to 3 30pm Email technical consortepl com Web www consortepl com IN...

Page 2: ...utral and earth Electrical supply for the CH06CPi and CH09i 12i models is either 240V single phase or 415V three phase neutral and earth Electrical supply for the CH15i model is 415V three phase neutr...

Page 3: ...lso be connected on a 230 240 volt 50Hz supply The maximum current draw for the 06CPi 09i 12i models are 25A 37 5A and 50A for single phase and approximately 8 3A 12 5A and 16 6A per phase for a three...

Page 4: ...own on Fig 3 Secure the wall bracket to the wall with suitable fix ings Ensure the position of this bracket will allow suitable clearances between the heater when fitted and adjacent walls Minimum of...

Page 5: ...e rating For controlling up to 2 heaters 3A up to 4 heaters 5A up to 10 heaters 13A For more connection details see figures 5 and 6 for the CH06CSi and CH06CPi CH09i 12i 15i models respectively The wi...

Page 6: ...of fan failure or an obstruction of the free airflow by two thermal cut outs If this happens the thermal cut outs effectively switch off the appliance The appliance will not operate until the thermal...

Page 7: ...7 CH06CSi Wiring Diagram 51000214 Iss 01...

Page 8: ...8 CH06CPi Wiring Diagram 51000214 Iss 01...

Page 9: ...9 CH09i 12i 15i Wiring Diagram 51000214 Iss 01...

Page 10: ...10 51000214 Iss 01...

Reviews: