To replace a switch in the control box

 

1. 

Switch off the mains supply 

2. 

Remove the switch box cover. 

3. 

Disconnect the wiring to the switch. 

4. 

Release the spring clips and push out the switch. 

5. 

Fit the replacement switch, reconnect the wiring and replace the cover. 

Electrical connections 

The  heater  is  suitable  for  connection  to  a  415 
volt 3 phase 50Hz supply.  . 
On full heat setting the load is 9, 12, 14 or 16kW 
depending of the model. 
The  connections  between  the  unit  and  remote 
switch box are shown on Fig 8. 

For safety reasons a good earth connection must AL-
WAYS  be  made  to  the  unit  and  the  control  box.    On 
the heater the earth terminal is adjacent to the termi-
nal block and is clearly marked with the symbol 

The  unit  should  be  wired  in  accordance  with  BS7671 
latest  edition  requirements  for  electrical  installations.  
The installer should ensure that a suitable fused isolat-
ing switch is connected in the mains supply. 

Fuses 

The motor and switch circuits are protected by two fuses which have a 3 amp rating.  Ensure that any 
replacement is of the correct size and rating. 

Spares 

It is essential when ordering spares or replacement parts to state the model number CA1509, CA1512, 
CA1514 or CA1516 and the serial number on the rating place fixed to the top of the unit. 
In the interest of progress the Company reserves the right to vary specifications from time to time with-
out notice.  The material listed is offered subject to the Company’s General Conditions of Sale, a copy 
of which can be obtained on request. 

41001304 Iss 01 

Electrical Data

 

CA1509

 

CA1512

 

CA1514

 

CA1516

 

Supply voltage

 

 

 

415V three phase 50Hz

 

415V three phase 50Hz

 

Total load

 

kW

 

9

 

12

 

14

 

16

 

A/pha

 

12.6

 

16.7

 

19.6

 

22.4

 

Motor power

 

W

 

60

 

Max Running current

 

Amps

 

0.6

 

Internal fuse size amps

 

Amps

 

3

 

External fuse size amps

 

A/pha

 

16

 

20

 

25

 

25

 

Cable terminal size

 

 

 

10mm

Max

 

Mains terminal block position

 

 

 

Centre of base unit.

 

Terminals N; L1; L2 & L3

 

Centre of base unit.

 

Terminals N; L1; L2 & L3

 

Control terminal block cable size

 

 

 

4mm

Max

 

Control terminal block position

 

 

 

Centre of base unit

 

Terminals 1-5

 

Centre of base unit.

 

Terminals 1-5

 

Control terminal block current

 

Amps

 

0.6

 