cartridge Dust collector

3.6.2 DUCT SILENCER INSTALLATION

a duct-type (in-line) silencer is designed to bolt 

directly to the blower outlet damper flange. Make 

certain there is adequate room for the silencer in 

the discharge direction. Provide at least 24” (61 

cm) of unobstructed space at the end of the silencer 

discharge. the air discharge should be directed into an 

open area, free of obstructions and with consideration 

for personnel safety.

CRUSH HAZARD

the silencer will require a separate support. Do not 

use the blower damper or outlet flange to support  

the silencer. apply silicone around the bolt holes of 

the connecting flanges, lift the silencer into position 

and secure with the hardware provided. install 

permanent supports (customer-supplied) and tighten 

all hardware before removing the lifting device. 

3.6.3 ROTARY AIR LOCK INSTALLATION

if a rotary air lock was ordered with the unit, the 

hopper discharge will have an adapter already bolted 

to it. Make certain the bolts connecting the adapter to 

the hopper discharge are securely tightened.
remove all packing from the rotary air lock and 

determine its appropriate position. Keep in mind 

required clearances, electrical connections and 

maintenance. apply sealant to the flange of the rotary 

air lock and to the adapter using 3/8” bolts, washers 

and lock washers.

ELECTRICAL SHOCK HAZARD

    Disconnect and lockout all power to the rotary air 

lock before servicing. all electrical connections 

should be made by a qualified electrician according 

to all applicable codes. refer to the nameplate and/

or documentation for voltage, amperage, cycle 

and proper wiring. refer to rotary air lock vendor 

documentation attached with air lock device.

MOVING PARTS

    there are moving parts on the rotary air lock. Do not 

allow any object to be placed in or near the rotary  

air lock during operation. Verify rotary air lock  

rotation matches rotation arrows affixed to assembly.

3.6.4 ABRASIVE INLET INSTALLATION

the abrasive inlet is designed to use the front access 

panel(s) of the Sfc Series modules as the inlet area 

to the unit. There are two styles available – a single 

or dual module abrasive inlet. each is designed to fit 

over the appropriate number of front access panels to 

serve as a single inlet point for one or two modules 

(refer to figure 12).

remove the front access panel(s) located above the 

QuickSeal filter access doors. Save the hardware. 

the hardware will be used to attach the abrasive inlet. 

remove any remaining gasket material from around 

the perimeter of the opening.
apply a 1/4” (6 mm) bead of sealant around the 

perimeter of the access opening in a “figure 8” 

pattern around the bolt holes. align the hole pattern 

on the abrasive inlet with the hole pattern on the unit 

and bolt together using the hardware removed earlier. 

fasten the inlet ducting securely to the abrasive inlet 

assembly.
the bottom plate of the abrasive inlet will serve as 

an inspection plate. if access to the abrasive inlet is 

required, remove and clean out the bottom plate of the 

inlet prior to servicing. Do not damage the ribbon of 

gasket and reuse after cleaning the gasket surfaces.

3.6.5  DRUM LID INSTALLATION

the drum lid package is an optional accessory for the 

Sfc Series dust collectors. refer to figure 13.
remove the drum lid package from it shipping  

carton. Place the drum lid on the 55-gallon (208 liter) 

drum or the 20-gallon (76 liter) drum. Slide the 14” 

(360mm) diameter hose over the drum lid and  

secure with hose clamp. Position the drum assembly 

under the unit, slide the hose up onto the 14” adapter 

collar on the hopper and secure it with a clamp.

 

!

  D A N G E R

!

 

WARNING

44-10046-0001

FIGURE 13

Drum Lid Installation

!

 

WARNING

Summary of Contents for UAS SFC Series

Page 1: ...Downward Flow Cartridge Dust Collector l Model SFC l PATENT NO 6 902 592 OWNER S MANUAL...

Page 2: ...when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL ________________...

Page 3: ...ogether Module Sections applies to 4 or more modules 6 3 4 Electrical Installation 11 3 4 1 Mounting the Controls 11 3 4 2 Solenoid Valve Enclosure Wiring 11 3 4 3 Heater Wiring 15 3 5 Compressed Air...

Page 4: ...al 24 5 3 Servicing the Compressed Air Components 25 5 4 Servicing the Direct Drive Blower and Motor System 25 5 5 Servicing Cartridge Media 25 5 6 Servicing Optional Return Air Safety Filters HEPA AS...

Page 5: ...t collector The unit should be inspected frequently and dirt removed to prevent excessive accumulation which may result in flash over or fire damage The SFC system should not be used to support person...

Page 6: ...r are recommended to be located outside the building in non traffic areas even though the dust collector is equipped with an explosion vent 2 INTRODUCTION Thank you for selecting UAS dust collection e...

Page 7: ...e pulse cleaning mechanism provides brief bursts of compressed air directed through the diaphragm valves toward the cartridge filter This pulsing action dislodges the collected particles from the medi...

Page 8: ...installation kit Hopper assemblies will be shipped in pieces and will need to be assembled at the site The hopper sections are shipped in pieces for field assembly Position the legs as shown in Figure...

Page 9: ...4 Revised 04 15 SFC Cartridge Dust Collector FIGURE 2 SFC Typical Single Unit Installation Diagram 44 10335 0001...

Page 10: ...5 Revised 04 15 SFC Cartridge Dust Collector FIGURE 3 Recommended Unit Clearances 44 10337 0001...

Page 11: ...mbly is equipped with four 1 2 13mm pry locations two holes on front flange and two holes on rear flange Refer to Figure 7 Detail C to aid in aligning the hopper flange with the module flange With fil...

Page 12: ...7 Revised 04 15 SFC Cartridge Dust Collector FIGURE 4 Single Hopper SFC 44 10309 0001...

Page 13: ...8 Revised 04 15 SFC Cartridge Dust Collector FIGURE 5 Multiple Hopper SFC 44 10309 0002...

Page 14: ...9 Revised 04 15 SFC Cartridge Dust Collector FIGURE 6 Multiple Hopper SFC 44 10309 0003...

Page 15: ...10 Revised 04 15 SFC Cartridge Dust Collector FIGURE 7 Multiple Modules SFC 44 10310 0001...

Page 16: ...itor DPM for continuous pulse cleaning Motor starter with Digital Pulse Control DPC for on demand pulse cleaning VFD with DPM for continuous pulse cleaning VFD with DPC for on demand pulse cleaning Re...

Page 17: ...12 Revised 04 15 SFC Cartridge Dust Collector FIGURE 8 SFC Pressure Gauge Installation 44 10333 0001 Rev A...

Page 18: ...13 Revised 04 15 SFC Cartridge Dust Collector FIGURE 9 Solenoid Wiring to Pulse Controls for 2 3 4 and 5 Tier Units...

Page 19: ...14 Revised 04 15 SFC Cartridge Dust Collector FIGURE 10 Pneumatic Valve Assembly 44 10332 0001...

Page 20: ...fitting sealant on all compressed air supply pipe fittings and connections 3 6 ASSEMBLY OF OPTIONAL EQUIPMENT 3 6 1 BLOWER PACKAGE INSTALLATION TIP OVER HAZARD Anchor dust collector to concrete pad pr...

Page 21: ...6 Revised 04 15 SFC Cartridge Dust Collector Figure 11 Legs Support Top Mount Blower 44 10331 0001 NOTE FOR BLOWERS 20 HP OR LARGER SUPPORT LEGS ARE REQUIRED TO BE INSTALLED UNDER THE CLEAN AIR PLENUM...

Page 22: ...17 Revised 04 15 SFC Cartridge Dust Collector Figure 12 Abrasive Inlet Installation 44 10338 0001...

Page 23: ...ing parts on the rotary air lock Do not allow any object to be placed in or near the rotary air lock during operation Verify rotary air lock rotation matches rotation arrows affixed to assembly 3 6 4...

Page 24: ...ons NOTE The hopper s is not designed for dust storage The slide gate should remain open during normal operation 3 6 6 INLET COVER AND BLANK COVER PLATE INSTALLATION Inlet collar and blank cover plate...

Page 25: ...20 Revised 04 15 SFC Cartridge Dust Collector Figure 16 EDAP Interconnection Figure 15 EDAP Installation 48 10007...

Page 26: ...shipping routine for an assembled SFC unit is with an enclosed box truck This type of truck will not be able to transport an assembled 4 high unit due to height restrictions within the vehicle When s...

Page 27: ...22 Revised 04 15 SFC Cartridge Dust Collector Figure 17 SFC Series Door Filter Installation 44 10329 0001...

Page 28: ...n 1 5 w g 25 127 mmAq At start up this reading is generally in the 1 3 w g 25 76 mmAq range Please list the reading here for future reference Initial dust collector differential pressure reading acros...

Page 29: ...m the inner door gasket Pull the QuickSeal door handle away from the dust collector until the handle makes a 90 angle with the door cover The filter access door is now in an unlatched position Lift th...

Page 30: ...TRIC SHOCK HAZARD All electrical work should be performed by a qualified electrician in accordance with local electrical codes Disconnect electrical power before installing or servicing any electrical...

Page 31: ...old or burst rupture panel While loosening the capture frame bolting take care to avoid the sharp edges of the rupture panel as these can cause severe cuts and or abrasions Remove the capture frame a...

Page 32: ...ip hold downs 3 5 Loosen nuts 9 holding flat clip supports 2 on internal door edge 7 Check flat Clip supports 2 as directed above Rotate 90 so flat clip support 2 is parallel with the door edge 7 6 Pu...

Page 33: ...ansformer etc Check for proper motor starter overload rating against full load amps on motor nameplate Adjust or replace overloads as required Ensure drum is properly sealed against drum lid package E...

Page 34: ...0 115 VAC supply voltage to the timer board and voltage output from timerboards to solenoid valves Consult DPM DPC Pulse Control Panel Installation and Operation Manual for additional assistance Reduc...

Page 35: ...30 Revised 04 15 SFC Cartridge Dust Collector 7 ILLUSTRATED PARTS FIGURE 21 SFC Series 44 10330 0001 FIGURE 22 SFC Series Explosion Vents...

Page 36: ...Lid 8A 45 10034 0020 20 Gallon Drum Lid 9 45 10022 0055 55 Gallon Quick Release Collar 9A 45 10022 0020 20 Gallon Drum Quick Release Collar 10 15 0233 14 Hose Clamp 11 15 0202 14 Flexible Duct 12 18 0...

Page 37: ...This page intentionally left blank...

Page 38: ...This page intentionally left blank...

Page 39: ...This page intentionally left blank...

Page 40: ...to goods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice Preside...

Reviews: