WS1CS & WS1.25CS Manual
Installer Display Settings
STEP 1I
- Press NEXT and
▲
simultaneously for 3 seconds.
STEP 2I
– Hardness: Set the amount of hardness in grains of hardness as calcium
carbonate per gallon using
▼
or
▲
. The default is 20 with value ranges from 1 to 150 in 1
grain increments. Note: The grains per gallon can be increased if soluble iron needs to be
reduced. This display will show “–nA–” if “FILTER” is selected in Step 2F or if ‘AUTO’
is not selected in Step 7S. Press NEXT to go to step 3I. Press REGEN to exit Installer Dis-
play Settings.
STEP 3I
– Day Override: When gallon capacity is set to off, sets the number of days
between regenerations. When gallon capacity is set to AUTO or to a number, sets the
maximum number of days between regenerations. If value set to “oFF” regeneration
initiation is based solely on gallons used. If value is set as a number (allowable range from
1 to 28) a regeneration initiation will be called for on that day even if suf
fi
cient number of
gallons were not used to call for a regeneration. Set Day Override using
▼
or
▲
:
• number of days between regeneration (1 to 28); or
• “oFF”.
See Setting Options Table for more detail on setup. Press NEXT to go to step 4I. Press
REGEN to return to previous step.
STEP 4I
– Next Regeneration Time (hour): Set the hour of day for regeneration using
▼
or
▲
. AM/PM toggles after 12. The default time is 2:00 a.m. This display will show “REGEN
on 0 GAL” if “on 0” is selected in Step 8S or Step 7F. Press NEXT to go to step 5I. Press
REGEN to return to previous step.
STEP 5I
– Next Regeneration Time (minutes): Set the minutes of day for regeneration
using
▼
or
▲
. This display will not be shown if “on 0” is selected in Step 8S or Step
7F. Press NEXT to exit Installer Display Settings. Press REGEN to return to previous
step.
To initiate a manual regeneration immediately, press and hold REGEN for three seconds.
The system will begin to regenerate immediately. The control valve may be stepped
through the various regeneration cycles by pressing REGEN .
General Operation
When the system is operating one of two displays will
be shown. Pressing NEXT will alternate between the
displays. One of the displays is always the current time
of day. The second display is one of the following: days
remaining or gallons remaining. Days remaining is the
number of days left before the system goes through a
regeneration cycle. Capacity remaining is the number of
gallons that will be treated before the system goes through
a regeneration cycle. The user can scroll between the
displays as desired.
If the system has called for a regeneration that will occur
at the preset time of regeneration, the words REGEN
TODAY will appear on the display.
When water is being treated (i.e. water is
fl
owing through
the system) the word “Softening” or “Filtering”
fl
ashes on
the display if a water meter is installed.
User Display Settings
OR
REGEN TODAY will
show if a regeneration
is expected “Tonight.”
STEP 1I
STEP 2I
STEP 3I
STEP 4I
STEP 5I
RETURN TO
NORMAL
MODE