Power Management
. To calibrate the pressure sensor properly, it must be disconnected from the valve in order to read atmosphere
pressure.
3.3.5.2
"
Confi
gure Outputs"
Menu
A
"short click"
on
"Right/output"
from the
"
Configur
e Outputs"
screen enters the
configu
ration of the selected
output.
Solenoid Output (SO) Field Descriptions:
"Display Name":
Use this
fie
ld to choose a unique name for each output.
"Type":
o
“CVM/CVP”
its PWM output (Pulse Width Modulation): this is the industry trade name for the management of
pulses sent to the opening/closing CVM/CVP pilots.
o
“Latching Output 1/0”
: Provide a pulse for 200ms by default open (1) or close (0) the bistable solenoid.
o
“Digital 1/0”
: Specifies that the output is either open or closed for the time specified in the boxes below.
Its use to provide power supply on CVM/CVP pilots (6VDC).
"Cycle Time":
The amount of time for one complete cycle of action for the opening/closing CVM/CVP pilots.
"Default Value":
The default active time of the CVM/CVP pilots during the cycle.
"Display on home page":
When this box is checked, the input is shown on Display panel.
3.3.5.3
"
Valve Configuration
"
Menu
The
"
Valve Configuration
"
screen includes the regulation blocks related to the loaded
ValvApps™.
Regulation blocks can be of the following types: