CLA-VAL
311C/D
Standard Solenoid Valve 3/2 Lucifer
`
CLA-VAL
Europe
www.cla-val.ch
3
-
ELE311TE
A 12/08
`
OPTION: EXPLOSION-PROOF SOLENOIDS II 2 G EEX DM IIC T4
Explosionproof solenoids with flameproof enclosure/encapsulation “dm”
According to ATEX directive 94/9/EC and Standards EN 50014, EN 50018, EN 50028 and EN 50281-1-1.
Application:
Control of solenoid valves intended for installations in hazardous areas in which explosive gas-atmospheres are present, i.e.
zones 1 or zones 2 (ATEX: Group II, apparatus categories 2G or 3G).
The enclosure of these explosion proofs solenoids "dm" is made entirely in synthetic material. All external metallic
components in contact with the atmosphere are made in stainless steel. The integrated sealing and O-rings assure the
degree of protection IP67. Therefore, these products took into account not only the suitability with hazardous areas but also
extremely corrosive environment, e. g. Chemical, Petrochemical and Refineries industries (CPR). Due to the compact size
and easy cable connection by screw terminals, these solenoids may be mounted in confined spaces.
Features:
The coil winding (copper wires of insulation Class H) and magnetic iron path are encapsulated in synthetic material Class H
and meet "m" protection. The connection box and cover of selected high quality synthetic material (Class H) in order to meet
the standard EN 50018 for type of protection "d" flameproof enclosure.
The cable gland assembly M20x1.5 makes part of
the "d" certificated enclosure.
The solenoids are provided with an embedded non-resetting thermal fuse to prevent
excessive heating, i.e. assuring the maximum allowed surface temperatures T5/T4. A varistor for peak voltages suppression
is potted-in, in Epoxy resin Class H.
Reference:
495905
Approval / Type of protection:
LCIE 02 ATEX 6451 X
Gas II 2 G – EEx dm IIC T4
Degree of protection:
IP67
Ambiant temperature:
-40 to +65 °C
Insulation Class:
H (180 °)
Electrical connection:
Electric connection is done in the connection box on an easily accessible
connector terminal. The introduction of the cable (Ø min 7mm, Ø max. 9mm,
section max. 2.5mm²) in the connection box passes by the built in M20x1.5
cable gland.
DC
Pn
(hot)
8 W
P
(cold) 20°C
9 W
Electr. Power:
AC
Pn
(holding)
8 W
Attraction cold
9 W
Nominal voltage:
6 to 110 VCC 12 to 240 VCA
Voltage tolerance:
± 10 % of the nominal voltage
Solenoid duty:
Continuous duty solenoid (ED 100%)