CLA-VAL
100-01 NGE
Main Valve HYTROL
`
CLA-VAL
Europe
www.cla-val.ch
1
-
HYN001DE
B 01/08
`
Simple, Reliable and Accurate
`
CLA-VAL SERIES 100
Main Function
The CLA-VAL 100-01 HYTROL Valve is a
hydraulically operated, diaphragm actuated, globe
or angle pattern valve.
It consists of three major components: body,
diaphragm assembly and cover. The diaphragm
assembly is the only moving part, guided top and
bottom by a precision machined stem. The disc
retainer and rubber disc form a drip-tight seal with
the renewable seat when pressure is applied
above the diaphragm (cover chamber).
The CLA-VAL 100-01 is the basic valve used in
nearly in all CLA-VAL Automatic Control Valves.
`
CLA-VAL 100-01
Principle of Operation
Full Open Operation:
When pressure in the cover
chamber is relieved to a lower
pressure or to atmosphere, the
pressure inlet opens the valve.
Tight Closing Operation:
When pressure from the inlet
pressure is applied to the cover
chamber, the valve closes drip-tight.
Modulating Control:
The valve is pressure operating
balanced. The CLA-VAL
"Modulating" Controls will allow the
valve to automatically compensate
for pressure changes.
`
Usual Main Valves
`
More Information
HYTROL Main Valve / HYTROL NGE-316
100-01
Sheet #
TYTAN Main Valve
100-01
5
Schematic
Diagram
HYN001TT
HYTROL Auxiliary Valve
000130TT
5
Quick Valve Selection
000121DE
ROLL SEAL Main Valve
100-42
5
Dimensions
000122DE-1
DELUGE Main Valve
100G
5
Pressure Ratings & Materials
000123DE
`
Other Functions : Please Contact CLA-VAL
There are 3 HYTROL body types:
NGE: New Globe Execution
GE: Globe Execution
AE: Angle Execution
Diaphragm
Cover
Disc retain &
Rubber disc
Stem
Body
Seat
Diaphragm
assembly
On/Off Control
On/Off Control
CLA-VAL Controls
Summary of Contents for 90-01