Antenna Connector
User Interface Screen
Safety Earth Ground
Jumper to Cover
DMX Cable Entry
Mains Cable Entry
Mains Input Terminals
DMX/RDM I/0 Terminals
USB Connector
Up
Enter
Down
Menu
Status LED
Figure 2: Face Panel Diagram
Slide the mating Mounting Bracket (attached to the Unit) into the Mounting Bracket Base until the
locking clip engages, and install the retaining Screw.
Cable or Conduit Entry
The unit enclosure is provided with ½” NPT entry holes fitted with liquid-tight cable grips for use
with outdoor use cables (by installer) for power and DMX connection. The recommended torque
for these cable grips is as follows:
Locking Nut
40-45 inch pounds
Sealing Nut
50-55 inch pounds
If outdoor use conduit is used instead, it is recommended that the conduit be sealed after
installation to prevent moisture entry, including free air exchange, in order to minimize the chance
of condensation buildup.
Face Panel