•
The rack is installed and secured to its location
Step 1
Install two front-mount brackets to the switch as follows:
a) Determine which end of the chassis is to be located in the cold aisle as follows:
•
If the switch has port-side intake modules (fan modules with burgundy coloring), position the switch so that its
ports will be in the cold aisle.
•
If the switch has port-side exhaust modules (fan modules with blue coloring), position the switch so that its fan
and power supply modules will be in the cold aisle.
If the power supply modules have white coloring, look at the fan modules to determine the airflow direction
for the switch.
Note
b) Position a front-mount bracket so that four of its screw holes are aligned to the screw holes on the side of the chassis.
You can align any four of the holes in the front rack-mount bracket to four of the six screw holes on the side
of the chassis (see the following figure). The holes that you use depend on the requirements of your rack
and the amount of clearance required for interface cables (3 inches [7.6 mm] minimum) and module handles
(1 inch [2.5 mm] minimum).
Note
Figure 4: Two Ways to Attach Rack-Mount Brackets and Guides on the Switch
Front rack-mount bracket aligned to the port
connections end of the chassis
5
Front rack-mount bracket aligned to the module end
of the chassis
1
Cisco Nexus 9332PQ NX-OS-Mode Switch Hardware Installation Guide
15
Installing the Switch Chassis
Installing the Switch