Clearance Requirements
Provide the chassis with adequate clearance between the chassis and any other rack, device, or structure so
that you can properly install the chassis. Provide the chassis with adequate clearance to route cables, provide
airflow, and maintain the switch. For the clearances required for an installation of this chassis in a four-post
rack, see the following figure.
Depth of the chassis
25.48 in (64.72 cm)
5
Chassis
1
Maximum extension of the bottom-support rails
36.0 in (91.0 cm)
6
Vertical rack-mount posts and rails
2
Depth of the front clearance area (equal to the
depth of the chassis).
25.48 in (64.72 cm)
7
Chassis width
17.3 in (43.9 cm)
3
Width of the front clearance area (equal to the
width of the chassis with two rack-mount
brackets that are attached to it).
19.0 in (43.3 cm)
4
Both the front and rear of the chassis must be open to both aisles for airflow.
Note
Cisco Nexus 9332D-GX2B NX-OS Mode Switch Hardware Installation Guide
10
Preparing the Site
Clearance Requirements