Cisco MGX 8950 Hardware Installation Guide
Release 3, Part Number 78-14147-02 Rev. A0, November 2002
Chapter 3 Installing a Cisco MGX 8950
Installation Procedures
Figure 3-33 Terminal Block on the DC PEM
Step 9
Attach the other end of the wire from
Step 10
Repeat
through
.
Step 11
Attach the end of the wire (from
) with the ring or space lug to the –48 VDC, as shown in
.
Step 12
Attach the other end of the wire from
to the DC source
Step 13
Use a Phillips-head screwdriver and two screws to attach the plastic cover over the terminal block on the
DC PEM.
Step 14
Turn on the power source and turn the DC PEM power switch on
Step 15
Verify that the fans are running by listening or feeling for air movement. The following LEDs should
be lit:
•
AC and DC LEDs on each power supply should be green.
•
DC OK LED on each DC PEM should be green.
•
Status LED on the PXM45 should be green.
•
Standby LED on each service module should be yellow.
Connect the External Clock
The section provides the following installation procedures to connect the external clock:
•
Connect the External Clock Using an RJ-45 Connection, page 3-51
•
Connect the External Clock Using a Wire-Wrap Adapter, page 3-51
Note
This step is optional.
48 VDC
return
Safety
ground
– 48 VDC
38228
-48V
RTN