The points to be inspected are:
1�-
Set the
SVGm
in STOP mode and open the main switch (
OFF
position).
2�-
Wait 1 minute for the capacitors to discharge.
3�-
Clean the ventilation grilles, removing the dust.
4�-
Check the status and torque of the electrical connections, as well as the mechanical attachment to
the wall.
5�-
Reset the standard maintenance meter, to do so:
Access the main setup screen.
Figure 77: Main configuration screen�
Press the
Edit key and enter the password used to access the maintenance screen (
Main-
tenance password:
8888
).
The screen shown in
Figure 78: Maintenance screen�
Press the
key to reset the maintenance meter.