7�6�- REACTIVE POWER OFFSET
Note:
This screen is not visible on the
“slave”
devices.
Note:
Feature available from HMI version 1.20 of the device.
On this screen, a fixed offset can be programmed that is added to the reactive power value calculated
to achieve the
cos
Φ
programmed in section
Figure 63: Configuration screen: Offset�
Example:
The device calculates that to achieve a
cos
Φ
= 1
it must generate
50 kvar
capacitive. An
offset of
30 kvar
inductive is programmed. It will thus generate
50-30 = 20 kvar
capacitive.
The offset value can be capacitive or inductive.
Table 28: Configuration values: Offset�
Offset
Minimum value
0 kvar
Maximum value
10000 kvar
Press the
key to access the next configuration step
Press the
key to access the main screen of the device without saving the configuration values.