23
Instruction Manual
RGU-10, RGU-10C
Table 5:LEDs description: Yellow LED�
Yellow LED
State
Description
Off
There is no pre-alarm trip.
On
Pre-alarm trip without reclosing.
On
flashing
Pre-alarm trip in reclosing situation.
4.4.- KEYBOARD FUNCTIONS
The device has 7 keys,
Figure 14
.
1�- Keys accessible with sealed cover and tool�
RESET
, Starts the equipment after a trip.
TEST
, Carries out a trip to check the proper operation of the relay.
PROG/PAG
, The function of the key depends on the duration of the touch.
Table 6:Operation of the PROG/PAG key�
Key
Operation
PROG/
PAG
Short press
Access to Pre-alarm programming.
Long press
Access to the programming of the device by Setup.
2�- Keys accessible with cover raised
Keys with dual function. With a long press, the device is entered to set the values. With a short
press, the option within a series of values defined in the device is selected.
SENSITIVITY
,
It allows to choose between the values of 30, 100, 300, 500 mA, 1 and 3 A
This scale can be extended using the SETUP program to add 5, 10 and 30 A to the
above values.
DELAY
,
It allows to choose between the values of 20,100, 200, 300, 400, 500, 750 ms and 1s.
This scale can be extended using the SETUP program to add 3, 5 y 10 s to the above
values.
This key also allows navigation within the SETUP MENU.
3�- Keys accessible with sealed cover and tool�
Flush buttons.
SAFETY
, This allows the output contacts’ polarity to be set for both the main relay and
the pre-alarm.
With normal safety (Std) the relay is activated with a fault, the status is NO.
With positive safety (+) the relay is activated on supplying the device and is deactivated