24
RGU-10 B, RGU-10 B RCM
Instruction Manual
6.- TECHNICAL FEATURES
Power supply AC
(1)
Rated voltage
230 V ~ ± 20%
Frequency
50 - 60 Hz
Consumption
6 VA
Installation category
CAT III 300 V
Power supply DC
(1)
Rated voltage
24 ... 125 V ± 20%
Consumption
4 W
CInstallation category
CAT III 300 V
(1)
Depending on model
Monitoring features
Sensitivity
0.1, 0.3, 0.5, 1, 3 A
Tripping delay
0.1, 0.2, 0.3, 0.4, 0.5, 0.75, 1, 5, 10 s
Relay output
Quantity
2
Type
Electronic class B
Rated voltage
250 V ~
Maximum switching voltage
400 V ~
Rated current
10 A ~
Instantaneous maximum current
15 A ~
Rated load in AC1
2500 VA
External trip / Reclose input
Type
Optocoupled
Maximum voltage
230 V ± 20% ~
Maximum consumption
0.7 W
Type of transformer to use
Sensitivity (IΔn)
Transformer
≥ 100 mA
WGS-20 TB, WGC-25 TB, WGC-35 TB
≥ 300 mA
WGC-55 TB
≥ 500 mA
WGC-80 TB, WGC-110 TB, WGC-140 TB, WGC-180 TB
Alarm range according to leakage current measured
Current
Lower limit
Upper limit
Type AC (sine)
0.8 x
Idn
1 x
Idn
Type A
Sine half wave
1.4 x
Idn
Sin half wave phase controlled (90º- 135º)
Type B
Smooth DC current
1.7 x
Idn
Sine current at 150 Hz
1 x
Idn
Sine current at 400 Hz
Sine current at 1000 Hz
1 x
Idn
1.3 x
Idn
User interface
Display
LCD
Keyboard
7 keys
LED
2 LEDs
Summary of Contents for RGU-10 B RCM
Page 1: ...INSTRUCTION MANUAL Residual current device and monitor RGU 10 B RGU 10 B RCM M087B01 03 20A...
Page 2: ...2 RGU 10 B RGU 10 B RCM Instruction Manual...
Page 27: ...27 Instruction Manual RGU 10 B RGU 10 B RCM 9 CE CERTIFICATE...
Page 28: ...28 RGU 10 B RGU 10 B RCM Instruction Manual...
Page 29: ...29 Instruction Manual RGU 10 B RGU 10 B RCM...
Page 30: ...30 RGU 10 B RGU 10 B RCM Instruction Manual...
Page 31: ...31 Instruction Manual RGU 10 B RGU 10 B RCM...
Page 32: ...32 RGU 10 B RGU 10 B RCM Instruction Manual...