34
RECmax Lpd
Instruction Manual
After exhausting the successive re-closing attempts unsuccessfully, the device is definitively switched
OFF. Reset from this status must be either by manual RESET or by remote reset through input EXT.
Input / Output contacts
EXT input
Voltage-free
AUX output
(6)
0.25 A - 230 V
TRIP output
(6)
0.25 A - 230 V
ON/OFF output
(6)
0.5 A - 230 V
Frequency
50 / 60 Hz
(6)
Installation category
AUX, TRIP
: CAT II 300V -
ON/OFF
: CAT III 300V
User interface
Display
LCD
Keyboard
3 keys
LED
2 LEDs
Environmental features
Operating temperature
-20ºC ... +70ºC
Storage temperature
-40ºC ... +75ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
IP20 - IP41 (cabinet panel mounted)
Mechanical features
Self-extinguishing capability
V0 (UL)
Screws
M3
Insertion force per pole
max 3N
Withdrawal force per pole
min 5N
Recommended torque
0.5 / 0.6 Nm
Length of stripped insertion cable
6 - 7.5 mm
Maximum cross-section
Flexible cable
Rigid cable
0.05 - 1.5 mm
2
0.05 - 2.5 mm
2
Attachment
DIN rail
Dimensions
RECmax Lpd 2 pole
RECmax Lpd 4 pole
Weight
550 g.
800
g.
Enclosure
PC + FV