57
Instruction Manual
RECmax-CVM
There are also some parameters (
) that make reference to the three phases at the same time
(OR function)� If one of these variables is selected, the alarm will be activated when any of the three
phases meets the programmed conditions�
Table 45:Codes of the multiple parameters for programming the alarm�
Type of parameter
Code
Phase-Neutral Voltage
200
Current
201
Active Power
202
Inductive Reactive Power
203
Capacitive Reactive Power
204
Power factor
205
Phase-Phase Voltage
206
% THD V
207
% THD A
208
Apparent Power
209
7�3�13�6� Communications
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 46:Modbus memory map: Communications
Communications
Configuration variable
Address
Valid data margin
Default value
Protocol
2742
0 :
Modbus
0
Peripheral number
2743
0 - 255
1
Transmission speed
2744
0:
9600
- 1:
19200
1
Parity
2745
0:
No parity
1:
Odd parity
2:
Even parity
0
Data bits
2746
0 :
8-bit
1:
7 bits
0
Stop bits
2747
0 :
1 stop bit
1:
2 stop bits
0
7�3�13�7� Nominal frequency
The
Functions
0x04
and
0x10
are implemented for this variable�
Table 47:Modbus memory map: Nominal frequency
Nominal frequency
Configuration variable
Address
Valid data margin
Default value
Nominal frequency
C360
0x32:
50 Hz
0x3C:
60 Hz
0x32