ANALYZER OF THE QUALITY OF ELECTRIC POWER SUPPLY
QNA-303 --
Page
19
6.1.- Operation setup of the QNA-303 analyzer
Points to be user-defined are following:
6.1.1.- Transformation ratios of voltage transformers
The
QNA-303
analyzer can take measurements through voltage transformers.
•
Voltage primary value / Voltage secondary value:
Set the
transformation ratio of voltage transformers used for measuring purposes.
In case of a direct measurement of the voltage (no voltage transformer
used) then just set 1/1.
6.1.2.- Features of the monitored electrical network
•
Rated voltage:
The rated voltage of the power system to be monitored by
the
QNA-303
. When the measurement is direct, that is, no voltage
transformer is used, then this voltage matches the network rated voltage. If
any .../110 V~ voltage transformer is used, then the rated voltage to be set
results from the application over the network rated voltage of the
transformation ratio. A right configuration of this point is essential since
permits setting the limits for the analysis of the electric power supply
quality.
•
Rated frequency:
The rated frequency of the power system to be
monitored by the
QNA-303
. This parameter is necessary for the calculation
of the signal RMS value in extreme quality networks.
•
Measurement type:
The
QNA-303
must be set according to the
distribution system to be monitored, whether with neutral conductor (4
wires) or without neutral conductor (3 wires). A proper setting of this point
is essential to assure a right detection of event occurrences. This choice
must also match the inner bridge position (See section 5.1.1.-)
6.1.3.- Data collection process features
•
File name:
Name of the file to be used for data recording (not modifiable).
•
Recording period:
Integration period for data recording into memory of all
selected parameters. Average, maximum and minimum values obtained
over this integration period will be recorded (See Section
¡Error! No se
encuentra el origen de la referencia.
).