Instruction Manual
DHC-96 CPM 1500
Example:
Clearing the energy totalisers:
Address
Function
Initial relay
address
Password
ID reset
ID value
CRC
01
0E
AACC
1111
01
FF
760D
6�3�6�- DEVICE CONFIGURATION VARIABLES
All the addresses of Modbus memory are in Hexadecimal.
For these variables is implemented the
Function 0x10�
6�3�6�1� Configuration of the input
Table 23: Modbus memory map: Configuration of the input�
Configuration of the input
Parameter
Format
Address
Valid data margin
Voltage display value
int
807
1000... 9999 V
Decimal point of the voltage
int
808
0:
xxxx -
1:
xxx.x -
2:
xx.xx -
3:
x.xxx
Voltage measurement range
int
80B
0:
150.0 V -
1:
300.0 V -
2:
600.0 V
3:
1000 V -
4:
1500 V
Current display value
int
809
1000... 9999 A
Decimal point of the current display
value
int
80A
0:
xxxx -
1:
xxx.x -
2:
xx.xx -
3:
x.xxx
Current input
int
80C
0:
50.00 mV -
1:
60.00 mV -
2:
75.00 mV
3:
100.0 mV -
4:
150.0 mV -
5:
200.0 mV
6:
250.0 mV -
7:
300.0 mV -
8:
400.0 mV
9:
600.0 mV
Decimal point for displaying voltage
int
82C
0:
xxxx -
1:
xxx.x -
2:
xx.xx
6�3�6�2� RS-485 communications
Table 24:Modbus memory map: RS-485 communications�
RS-485 communications
Parameter
Format
Address
Valid data margin
Modbus address
int
802
1... 247
Baud rate
int
803
0:
2400 bps -
1:
4800 bps -
2:
9600 bps -
3:
19200 bps-
4:
38400 bps
(3)
Data format
int
804
0:
n,8,1 : no parity, 8 data bits, 1 stop bit
1:
o,8,1 : odd parity, 8 data bits, 1 stop bit
2:
e,8,1 : even parity, 8 data bits, 1 stop bit
3:
n,8,2 : no parity, 8 data bits, 2 stop bit
(3)
Option available from version 1014 of the device software.
Summary of Contents for DHC-96 CPM
Page 1: ...INSTRUCTION MANUAL DC Multimeter DHC 96 CPM 1500 M331B01 03 22B...
Page 2: ...2 DHC 96 CPM 1500 Instruction Manual...
Page 50: ...50 DHC 96 CPM 1500 Instruction Manual 10 CE CERTIFICATE...
Page 51: ...51 Instruction Manual DHC 96 CPM 1500...
Page 52: ...52 DHC 96 CPM 1500 Instruction Manual...