6�3�5�- DEVICE CONFIGURATION VARIABLES
For these variables is implemented the
Function
0x10�
6�3�5�1� Configuration of the input
Table 40:Modbus memory map :
Configuration of the input
Configuration of the input
Variable
Format
Address
Valid data margin
Display value
int
809
1 ... 9999
Decimal point of the display value
int
80A
0:
xxxx -
1:
xxx.x -
2:
xx.xx -
3:
x.xxx
Units of the display value
int
806
0:
A -
1:
kA
Measurement range
int
80B
DHC-96 mAdc
:
0:
0 ... 20 mA -
1:
4 ... 20 mA
2:
± 20 mA
DHC-96 Adc
:
0:
0 ... 1A -
1:
0 ... 5A
6�3�5�2� RS-485 communications
Table 41:Modbus memory map :
RS-485 communications
RS-485 communications
Variable
Format
Address
Valid data margin
Modbus address
int
802
1 ... 247
Baud rate
int
803
0:
2400 bps -
1:
4800 bps -
2:
9600 bps -
3:
19200 bps
Data format
int
804
0:
n,8,1 : no parity, 8 data bits, 1 stop bit
1:
o,8,1 : odd parity, 8 data bits, 1 stop bit
2:
e,8,1 : even parity,
8 data bits, 1 stop bit
3:
n,8,2 : no parity,
8 data bits, 2 stop bit
6�3�5�3� Analog output
Table 42:Modbus memory map : Analog output
Analog output
Variable
Format
Address
Valid data margin
Reading for the end of the analog
output (
fs
)
int
815
0.5 x
A
(1)
≤
fs
≤ 1.2 x
A
(1)
Reading for the start of the analog
output (
ds
)
int
816
0
≤
ds
≤ 0.5 x
A
(1)
Type of output
int
817
0:
4 ... 20 mA
1:
0 ... 20 mA
2:
4 ...12 ... 20 mA
(1)
In the
DHC-96 mAdc
model the variable
A
has a value of 2000, in the
DHC-96 Adc
model has a value of 5000 for the
measurement range of
5.000
and 1000 for the measurement range of
1.000
.
38
DHC-96 mAdc, DHC-96 Adc
Instruction Manual
Summary of Contents for DHC-96 Adc
Page 1: ...INSTRUCTION MANUAL M227B01 03 22A DC Ammeter DHC 96 mAdc DHC 96 Adc...
Page 2: ...2 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 44: ...10 CE CERTIFICATE 44 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 45: ...45 Instruction Manual DHC 96 mAdc DHC 96 Adc...
Page 46: ...46 DHC 96 mAdc DHC 96 Adc Instruction Manual...