9
Instruction Manual
DCP-96 Aac
of
0�25 A
.
If more than one device is connected to the current transformer, they must be connected in series.
Before disconnecting the current measurement connection cables, be sure to disconnect the trans-
former’s primary cables and bridge the secondary.
The device can operate in three-wire, three-phase mode or four-wire, three-phase mode, the user
selecting the corresponding connection mode according to the installation. An incorrect type of con-
nection or an error in phase sequence may cause measurement errors.
3�3�- DEVICE TERMINALS
Table 4: List of DCP-96 Aac terminals�
Device terminals
1:
L/+
, Power supply
6: I2 S1
, Current input L2
2:
N/-
, Power supply
7: I2 S2
, Current input L2
4: I1 S1
, Current input L1
8: I3 S1
, Current input L3
5: I1 S2
, Current input L1
9: I3 S2
, Current input L3