23
Instruction Manual
DCP-96 Aac
7.- TECHNICAL FEATURES
AC Power supply
(1)
Rated voltage
80 ... 270 V ~
Frequency
50 / 60 Hz
Consumption
1 ... 4 VA
Installation category
CAT III 300V
DC Power supply
(1)
Rated voltage
80 ... 270 V
18 ... 36 V
Consumption
0.5 ...0.7 W
0.7 ...0.8 W
Installation category
CAT III 300V
(1)
Depending on model:
DCP-96 Aac
Model
Power supply
80 ��� 270 V ~
80 ��� 270 V 18 ��� 36 V
M22450
-
M224500030000
-
-
Current measurement circuit
Rated current (In)
1 A / 5 A ~
Frequency measuring margin
45 ... 65 Hz
Overcurrent
1.2 In continuous - 10 In Instantaneous (5 s)
Consumption
< 0.2 VA (per phase)
Impedance
< 20 mΩ
Installation category
CAT III 300V
Accuracy
Current measurement
0.2 % ± 1 digit
Frequency measurement
± 0.01 Hz
User interface
Display
LCD
Keyboard
3 keys
Environmental Features
Operating temperature
-25ºC ... +70ºC
Storage temperature
-40ºC ... +85ºC
Relative humidity (without condensation)
≤ 95%
Maximum altitude
2000 m
Protection degree
Front: IP54, Rear case: IP20
Pollution degree
2
Mechanical characteristics
Terminals
1, 2, 4 ... 9, 58 ... 60
2.5 mm
2
0.5 Nm
Flat (SZS 0.6x3.5)
Dimensions
(mm)
Weight
202 g.
Enclosure
pc + abs