4�6�-PROGRAMMING
Fromtheprogrammingmenuyoucan:
Definethetransformationratios�
ProgramtheratioofkgCO
2
carbonemissionsofthetwotariffs�
Programthecostratioofthetwotariffs�
Programthemaximumdemandparameters�
Deletetheenergymetersandthemaximumandminimumvalues�
Modifythedisplay'sbacklight�
Programthedigitaloutput�
The
CVM-C5
doesnotrecordprogrammingchangesuntiltheprogrammingiscomplete�Ifthe
deviceisRESETbeforefinishingtheprogrammingornokeyispressedfor30seconds,the
configurationwillnotbestoredinthememory�
The
CVM-C5
doesnottakeanymeasurementsduringprogramming�
Toentertheprogrammingmenupressthe
keyfor3seconds�
Andpress
toaccessthefirstprogrammingpoint�
4�6�1� Primary voltage
Onthisscreenthevoltagetransformerprimaryisprogrammed�
Toenterormodifythetransformerprimaryvalue,pressthe
keyrepeatedly,increasingthevalueoftheflashingdigit�
Whentheon-screenvalueisthatdesired,pressthe
keyto
gotothenextdigittomodifytheothervalues�
Ifyoupressthe
keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou
canmodifythepreviouslyprogrammedvaluesagain�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2
secondsandtheprogrammedvalueisdeleted�
Maximum programming value: 99999.
Minimum programming value: 0.
26
CVM-C5
Instruction Manual