4�6�4� Secondary current
(
only the model
CVM-C5-IC
)
Onthisscreenthecurrenttransformersecondaryisselected�
Usethe
keytojumpbetweenthetwopossibleoptionsfor
thecurrenttransformersecondary(1Aor5A)�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Note:
Ifthevoltageratiotogetherwiththeprogrammedcurrentratioexceedsthemaximum
powervaluethatcanbemeasuredbythedevice,itwillreturntotheprimaryvoltage
programmingstepwhenyoupressthe
key�
Nota :
Toapplythechangetothesecondcurrenttransformerisnecessarytoresetthecomputer�
4�6�5� Measurement system
Onthisscreenthemeasurementsystemtobeusedinthe
installationisselected�
The
keyjumpsbetweenthedifferentoptions
Three-phasenetworkmeasuringwitha4-wireconnection�
Three-phasenetworkmeasuringwitha3-wireconnection�
Three-phasenetworkmeasuringwitha3-wireconnectionandtransformersinan
ARONconnection
�
Two-phasenetworkmeasuringwitha3-wireconnection�
Phase-to-phasesingle-phasenetworkmeasuringwitha2-wireconnection�
Phase-to-neutralsingle-phasenetworkmeasuringwitha2-wireconnection�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
28
CVM-C5
Instruction Manual