cos
φ
:
Maximum value:
1.00
Minimum value:
0.50
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
5�25�- VOLTAGE THD ALARM
In this point the thresholds above which the Voltage THD alarm
(
E08
)
is activated can be configured.
The programmed values are useful for the 3 phases which the device measures.
Note:
The alarm must be enabled (
).
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The parameters to be configured are:
The
Lo
value
:
when the device exceeds this value for 30 minutes, alarm
E08
is triggered,
and if alarm
E11
is enabled, the
Computer SMART III
device enters the
No Connection
status
and activates
alarm
E11
.
The
HI
value:
if the device exceeds this value for 30 seconds, alarm
E08
is triggered, and
if alarm
E12
is enabled, the
Computer SMART III
device enters the
Disconnection
status and
activates
alarm
E12
.
If the device falls back under the
Lo
value during 10 minutes, it deactivates the alarms and returns
to the normal operating status.
99
Instruction Manual
Computer SMART III
Summary of Contents for Computer SMART III 12
Page 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Page 2: ...2 Computer SMART III Instruction Manual...
Page 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III...
Page 112: ...112 Computer SMART III Instruction Manual...