Instruction Manual
CBS-400B
WGB
WGB
WGB
WGB
CBS-400B
RJ45
Channel 1
Channel 2
Channel 3
Channel 4
Figure 12: CBS-400B - WGB connection�
Note:
If a RJ45 connection cable other than the one supplied with the
WGB
is used, it must have a
cross-section of 4 x 2 x AWG24/7. The maximum distance from the
CBS-400B
to the furthest
WGB
must be of 9 metres.
The
CBS-400B
detects the transformers automatically, assigning each of them a specific channel.
Connect the
CBS-400B
output relays to each of the installed channels.
If the automatic channel connection carried out by the device does not match the installation carried
out in the output relays, the numbering of the channels in the
CBS-400B
can be changed without
modifying the installation (see
).
If the installation is modified and it involves new transformer, a replacement of the
WGB
... the
CBS-
400B
will detect this change and light the screens in yellow, see
"5.2.- PROBLEMS OR CHANGES IN THE
�
Figure 13: Change in the installation�