Einbau- und Betriebsanleitung
Installation and Operating instructions
Instructions de montage et de service
6139-8010
07/2018
Figure 7- spring closing
17.
Slide the spiral spring and the actuating pin until it is in the correct position and the right stroke (see figure 8) has been set on the lever scale.
Figure 8
Note:
After assembling the SR 1000 L move the drive from 0% to 100% of the stroke. In both positions at 0% and 100% the lever may not
touch the end stop at the back of the SR 1000 L. See figure 9. If there is contact with the end stop move the actuating pin toward the
pivot point of the lever.
Figure 9
18.
With the actuating pin in its correct position tighten the hexagonal nut on the actuating pin.
5.
Tubing
Note:
•
Select a suitable compressor as the compressed air supply to prevent moisture, oil or dust from entering.
•
We recommend installing a pressure regulator before the SR 1000 L supply pressure input.
Stroke 30 mm
Stroke 60 mm
No contact