Harmonic set point
It should be noted that no V
peak
of any phase can exceed the 400 V, i.e., after adding harmonics
to the fundamental voltage, the resultant wave cannot exceed 400 V
peak
.
The maximum set point value can see below:
Harmonic
% of set point
Harmonic
% of set point
1
100
7
100
2
100
8
100
3
100
9
100
4
100
11
50
5
100
13
10
6
100
15
10
Parameters and limits (DC mode)
Parameter
Allowed range of values
Voltage
[0 , +750]
4.3.2.
Faults Generation (FG)
This mode allows the user to define and apply faults in the grid previously generated with the
CV mode.
Parameters and limits
In FG mode, the user can modify the value of the following fault general parameters as long as
it is within the specified range:
Parameter
Allowed range of values
Fault duration
1ms – 24h
Fault repetition
Minimum 1s
Fault delay (β)
0 - 360 °
The specified fault will start when the trigger is activated.
The procedure is as follows:
FAULT
FAULT
NO FAULT
NO FAULT
TRIGGER 0V
U
β
FAULT DURATION
FAULT
REPETITION
TRIGGER 0V
U
β