CIAT V3000 KNX Control Manual Download Page 8

Note: 

To perform a diagnostic, you must use a display terminal.
To enter diagnostic mode, you need to press the ventilation 

 and 

 buttons simultaneously for 5 seconds.

The parameter is selected by pressing the

 

 and 

. buttons. To consult a parameter value, you need to press the standby 

button

.

To exit diagnostic mode, press the ventilation button

 

Diagnostic

Name

Explanation

d01

Individual address

d02

Master address

Only valid for configuration in Push Button mode (see KNX Bus manual NA 08.51)

d03

Zone number

d04

Application type

1 = 2-Wire

2 = 2-pipe

21 = 2-Pipe/2-Wire

22 = 2 Tubes Froid + radiateur

23 = 2 tubes + convecteur élec.

4 = 4-pipe

41 = 4-Pipe/2-Wire

Parameter

Name

Explanation

Setting range

Default value

P55

Heating electrical power (based 

on 230 V)

If an electric heater is used, the power (in kW) must be indicated 

in this parameter, rounded up to the nearest 100W. Used for 

certain energy consuming applications 

0…20,0 résolution de 0,1

2.0

P56

LS power

The low speed ventilation power must be indicated in this 

parameter, rounded up to the nearest 5W.

Used for certain energy consuming applications

5…990

increments of 5

50

P57

MS power

The medium speed ventilation power must be indicated in this 

parameter, rounded up to the nearest 5W.

Used for certain energy consuming applications

5…990

increments of 5

75

P58

HS power

The high speed ventilation power must be indicated in this 

parameter, rounded up to the nearest 5W. Used for certain energy 

consuming applications

5…990

increments of 5

75

P59

Hot water coil nominal capacity

Nominal capacity (in kW) of the hot water coil, rounded up to the 

nearest 100W. Used for certain energy consuming applications

0…99.0 resolution

of 0.1

100

P60

Cold water coil nominal capacity

Nominal capacity (in kW) of the cold water coil, rounded up to the 

nearest 100W. Used for certain energy consuming applications

0…99.0 resolution

of 0.1

2.0

P62

Base outdoor temperature

Lowest outdoor temperature for electric heater power limiting

-35…+5

-10

P64

Setpoint deviation from outdoor 

temperature

Max difference between cold setpoint and outdoor temperature

0 = Inactive

0…20

6

P67

Battery/coil use authorisation

1 = hyd electric

2 = hydraulic only

3 = electric only

1:2:3

Depending on 

application

P93

Period for filter maintenance

At the end of this ventilation time, the maintenance pictogram 

appears on the screen for filter replacement. This pictogram does 

not stop control:

0 = Inactive

1…200 = time in days (in HS equivalent)

0…200

0

P94

Temperature displayed in °C or °F

1 = Temperature displayed in °C

2 = Temperature displayed in °F

1:2

1

P95

Temperature displayed on terminal

Actual temperature display on the indoor environment device 

LCD:

1 = Setpoint

2 = Measurement

1:2

2

P96

Setpoint offset value display

Display of actual temperature offset value:

1 = Not displayed (bar graph)

2 = Display bar graph

3 = Display se bar graph*

1:2:3

1

(*) The absolute setpoint displayed corresponds to the heating requirements calculated by the V3000: 
- if the room temperature (°C) > current cooling setpoint: the cooling setpoint is displayed
- if the room temperature (°C) > current heating setpoint: the heating setpoint is displayed.

5 - DIAGNOSTIC

  EN7515935-00 

 EN - 6 

Summary of Contents for V3000 KNX

Page 1: ...V3000 KNX 03 2017 EN7515935 00 C o n t r o l m a n u a l...

Page 2: ......

Page 3: ...IC 6 6 AIR TEMPERATURE MEASUREMENT 10 7 SPECIFICATIONS OF SENSORS USED BY THE V3000 10 8 WATER TEMPERATURE MEASUREMENT 10 9 CONTROL ALGORITHM 11 10 CONNECTING THE FRAME CONTACT 12 11 FRESH AIR 13 12 M...

Page 4: ...etpoint and also access the set up and diagnostic values Standby button This enables you to change the operating mode comfort standby economy frost protection according to the chosen set up Ventilatio...

Page 5: ...up Ventilation 1 2 or 3 ventilation symbols displayed simultaneously to indicate LS MS or HS If auto is selected the AUTO symbol appears in addition to the ventilation symbols If AUTO selected the LE...

Page 6: ...increments of 0 5 19 0 P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5 40 increments of 0 5 26 0 P04 Heating Standby setpoint Setpoint for heating control in Standby mode...

Page 7: ...ically restarted 0 1 2 3 0 P47 Operating mode activated by standby button on user terminal 1 Comfort Frost protection 2 Comfort Eco 3 Comfort Standby 1 2 3 1 P48 Comfort override delay Override to rem...

Page 8: ...of 5 75 P59 Hot water coil nominal capacity Nominal capacity in kW of the hot water coil rounded up to the nearest 100W Used for certain energy consuming applications 0 99 0 resolution of 0 1 100 P60...

Page 9: ...17 Heating heat consumption Calculated heat consumption of heating coil display unit hundred kWh d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil display unit...

Page 10: ...versa If the controller has just been supplied wait for system initiation 6 mins Check the electrical connection of the valves refer to wiring diagram No heating Check that The hot setpoint T C is gre...

Page 11: ...condensates on the cooling coil This alarm is present as long as there is condensation present on the cooling coil Check the water temperature E15 Slave cut off from master No dialogue between a mast...

Page 12: ...bypass often called a 4 way valve Sensor Changeover operating algorithm If the changeover sensor measures water temperature greater than 7 C adjustable in P27 at ambient temperature the water is deeme...

Page 13: ...P48 24 5 the setpoint overrides are stored in all operating scenarios The current fan speed is not memorized and returns to AUTO Operating mode activated by standby button According to parameter P47 p...

Page 14: ...2 Presence contact comfort Eco local override impossible 3 Presence contact comfort Standby local override impossible 4 Condensate pump alarm fan coil unit switched off and cold valve closed 5 Fan un...

Page 15: ...y mechanism being triggered 11 FRESH AIR Parameters P00 and configuration procedure Diagnostic d01 and d02 The V3000 may perform the master slave function via 3 different ways Master slave by hot cold...

Page 16: ...n to 1 5 mins It is completely finished when the fixed display Add 0 appears d To return to normal display press e If the display Err appears an error has occurred Check The bus wiring Its supply Para...

Page 17: ...ave loop a Start with the slave To switch to configurator mode press buttons for 5 seconds Press for 5 seconds until the display dEL flashes b Go on to the master Perform the same operation as above c...

Page 18: ...elow Switch the radio receiver to configuration mode pressing its button for 3 seconds until the green LED starts flashing more slowly On the remote control Remove the insulation tab on the batteries...

Page 19: ...up to 8 terminal units with a single remote control each terminal unit must be equipped with a radio frequency receiver To configure Set P00 to 0 on all the controllers in the master slave loop defaul...

Page 20: ...a Blank terminal b Wall mounted dial terminal 14 TECHNICAL SPECIFICATIONS EN7515935 00 EN 18...

Page 21: ...c Display terminal d Radio frequency receiver EN EN 19 EN7515935 00...

Page 22: ...the room the connection to the controller is provided by means of flexible wires with a maximum length of 30 m and section 1 mm 2 conductors see terminal 1 and 2 of the regulator It is essential to u...

Page 23: ......

Page 24: ...in mind CIAT reserves the right without notice to proceed with any technical modification Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 i...

Reviews: