Note:
To perform a diagnostic, you must use a display terminal.
To enter diagnostic mode, you need to press the ventilation
and
buttons simultaneously for 5 seconds.
The parameter is selected by pressing the
and
. buttons. To consult a parameter value, you need to press the standby
button
.
To exit diagnostic mode, press the ventilation button
Diagnostic
Name
Explanation
d01
Individual address
d02
Master address
Only valid for configuration in Push Button mode (see KNX Bus manual NA 08.51)
d03
Zone number
d04
Application type
1 = 2-Wire
2 = 2-pipe
21 = 2-Pipe/2-Wire
22 = 2 Tubes Froid + radiateur
23 = 2 tubes + convecteur élec.
4 = 4-pipe
41 = 4-Pipe/2-Wire
Parameter
Name
Explanation
Setting range
Default value
P55
Heating electrical power (based
on 230 V)
If an electric heater is used, the power (in kW) must be indicated
in this parameter, rounded up to the nearest 100W. Used for
certain energy consuming applications
0…20,0 résolution de 0,1
2.0
P56
LS power
The low speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W.
Used for certain energy consuming applications
5…990
increments of 5
50
P57
MS power
The medium speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W.
Used for certain energy consuming applications
5…990
increments of 5
75
P58
HS power
The high speed ventilation power must be indicated in this
parameter, rounded up to the nearest 5W. Used for certain energy
consuming applications
5…990
increments of 5
75
P59
Hot water coil nominal capacity
Nominal capacity (in kW) of the hot water coil, rounded up to the
nearest 100W. Used for certain energy consuming applications
0…99.0 resolution
of 0.1
100
P60
Cold water coil nominal capacity
Nominal capacity (in kW) of the cold water coil, rounded up to the
nearest 100W. Used for certain energy consuming applications
0…99.0 resolution
of 0.1
2.0
P62
Base outdoor temperature
Lowest outdoor temperature for electric heater power limiting
-35…+5
-10
P64
Setpoint deviation from outdoor
temperature
Max difference between cold setpoint and outdoor temperature
0 = Inactive
0…20
6
P67
Battery/coil use authorisation
1 = hyd electric
2 = hydraulic only
3 = electric only
1:2:3
Depending on
application
P93
Period for filter maintenance
At the end of this ventilation time, the maintenance pictogram
appears on the screen for filter replacement. This pictogram does
not stop control:
0 = Inactive
1…200 = time in days (in HS equivalent)
0…200
0
P94
Temperature displayed in °C or °F
1 = Temperature displayed in °C
2 = Temperature displayed in °F
1:2
1
P95
Temperature displayed on terminal
Actual temperature display on the indoor environment device
LCD:
1 = Setpoint
2 = Measurement
1:2
2
P96
Setpoint offset value display
Display of actual temperature offset value:
1 = Not displayed (bar graph)
2 = Display bar graph
3 = Display se bar graph*
1:2:3
1
(*) The absolute setpoint displayed corresponds to the heating requirements calculated by the V3000:
- if the room temperature (°C) > current cooling setpoint: the cooling setpoint is displayed
- if the room temperature (°C) > current heating setpoint: the heating setpoint is displayed.
5 - DIAGNOSTIC