Faults are automatically released once the problem related to the fault is resolved (sensor replaced…).
*Only the "Filter" fault requires manual release - to do so: 

 

- replace or clean the filter

 

- In the Diagnostic menu, access d19 "Filter maintenance time meter"

 

- Set this meter to 0 by pressing and holding the 

button for 5 seconds.

 

- Go back out of the diagnostic menu

 

- The alarm is released.

Alarm code

Diagnostic

Solutions

E07

Replace filter

The triggering time for this alarm can be set under P93

It is released in D19 by setting this meter to O*

E08

Supply air sensor fault or absent (P78=2)

Check the sensor, its wiring at S1 and the corresponding parameter

E09

return sensor fault (P24=0)

Check the sensor, its wiring at S1

E10

indoor environment sensor fault (P24=1)

Check the condition and wiring of the room terminal 

E11

Centralised changeover via KNX not received

Check the bus wiring, its supply, the KNX links with the Building Management System 

supplier

E12

fresh air frost protection alarm (supply air safety 

device)

Check the hot water temperature, the hot valve 

E13

fresh air frost protection alarm (safety thermostat)

Check the hot water temperature, the hot valve, the condition of the antifreeze thermostat

E14

condensation alarm

The terminal unit is in anti-condensation operating sequence following the appearance of 

condensates on the cooling coil. This alarm is present as long as there is condensation 

present on the cooling coil. Check the water temperature 

E15

Slave cut off from master

No dialogue between a master and a slave. 

Check the bus (connections, supply)

Check the Master controller supply

E16

condensate drain pump alarm

Check the condensate pump 

E17

general alarm

Check the condition of the contacts on D1-C and D2-C

E18

Fan unit alarm

Check the condition of the fan unit 

Check the condition of the contacts on D1-C and D2-C

E19

active temperature sensor fault

the 2 possible control sensors are faulty

Check the condition and wiring of the temperature sensors wired to the controller 

Check the condition and wiring of the wall-mounted room terminal 

E20

condensation sensor S3 fault

Check the condition and wiring of the anti-condensation sensor at S3-C

E21

Master or Slave not configured

Appears when configuring Master/Slave using push button until the master or slave is 

configured

E22

no other Push button product selected on the bus

Configure all products that need to be interlinked to create a Master/slave cluster

E23

impossible to connect to selected push button product

Check that the products in push button configuration are mutually compatible 

Check the bus, its supply, its wiring and the master/slave parameter (P00) on each product 

to be configured

--

No Alarm

With:
 

E00: alarm does not switch off the terminal unit. (E07 to E15)

 

E00:

 alarm locks the terminal unit off. (E16 to E23)

EN

 

 

EN - 9 

EN7515935-00

Summary of Contents for V3000 KNX

Page 1: ...V3000 KNX 03 2017 EN7515935 00 C o n t r o l m a n u a l...

Page 2: ......

Page 3: ...IC 6 6 AIR TEMPERATURE MEASUREMENT 10 7 SPECIFICATIONS OF SENSORS USED BY THE V3000 10 8 WATER TEMPERATURE MEASUREMENT 10 9 CONTROL ALGORITHM 11 10 CONNECTING THE FRAME CONTACT 12 11 FRESH AIR 13 12 M...

Page 4: ...etpoint and also access the set up and diagnostic values Standby button This enables you to change the operating mode comfort standby economy frost protection according to the chosen set up Ventilatio...

Page 5: ...up Ventilation 1 2 or 3 ventilation symbols displayed simultaneously to indicate LS MS or HS If auto is selected the AUTO symbol appears in addition to the ventilation symbols If AUTO selected the LE...

Page 6: ...increments of 0 5 19 0 P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5 40 increments of 0 5 26 0 P04 Heating Standby setpoint Setpoint for heating control in Standby mode...

Page 7: ...ically restarted 0 1 2 3 0 P47 Operating mode activated by standby button on user terminal 1 Comfort Frost protection 2 Comfort Eco 3 Comfort Standby 1 2 3 1 P48 Comfort override delay Override to rem...

Page 8: ...of 5 75 P59 Hot water coil nominal capacity Nominal capacity in kW of the hot water coil rounded up to the nearest 100W Used for certain energy consuming applications 0 99 0 resolution of 0 1 100 P60...

Page 9: ...17 Heating heat consumption Calculated heat consumption of heating coil display unit hundred kWh d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil display unit...

Page 10: ...versa If the controller has just been supplied wait for system initiation 6 mins Check the electrical connection of the valves refer to wiring diagram No heating Check that The hot setpoint T C is gre...

Page 11: ...condensates on the cooling coil This alarm is present as long as there is condensation present on the cooling coil Check the water temperature E15 Slave cut off from master No dialogue between a mast...

Page 12: ...bypass often called a 4 way valve Sensor Changeover operating algorithm If the changeover sensor measures water temperature greater than 7 C adjustable in P27 at ambient temperature the water is deeme...

Page 13: ...P48 24 5 the setpoint overrides are stored in all operating scenarios The current fan speed is not memorized and returns to AUTO Operating mode activated by standby button According to parameter P47 p...

Page 14: ...2 Presence contact comfort Eco local override impossible 3 Presence contact comfort Standby local override impossible 4 Condensate pump alarm fan coil unit switched off and cold valve closed 5 Fan un...

Page 15: ...y mechanism being triggered 11 FRESH AIR Parameters P00 and configuration procedure Diagnostic d01 and d02 The V3000 may perform the master slave function via 3 different ways Master slave by hot cold...

Page 16: ...n to 1 5 mins It is completely finished when the fixed display Add 0 appears d To return to normal display press e If the display Err appears an error has occurred Check The bus wiring Its supply Para...

Page 17: ...ave loop a Start with the slave To switch to configurator mode press buttons for 5 seconds Press for 5 seconds until the display dEL flashes b Go on to the master Perform the same operation as above c...

Page 18: ...elow Switch the radio receiver to configuration mode pressing its button for 3 seconds until the green LED starts flashing more slowly On the remote control Remove the insulation tab on the batteries...

Page 19: ...up to 8 terminal units with a single remote control each terminal unit must be equipped with a radio frequency receiver To configure Set P00 to 0 on all the controllers in the master slave loop defaul...

Page 20: ...a Blank terminal b Wall mounted dial terminal 14 TECHNICAL SPECIFICATIONS EN7515935 00 EN 18...

Page 21: ...c Display terminal d Radio frequency receiver EN EN 19 EN7515935 00...

Page 22: ...the room the connection to the controller is provided by means of flexible wires with a maximum length of 30 m and section 1 mm 2 conductors see terminal 1 and 2 of the regulator It is essential to u...

Page 23: ......

Page 24: ...in mind CIAT reserves the right without notice to proceed with any technical modification Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 i...

Reviews: