2 - CLOSE-UP OF DISPLAY TERMINAL SCREENS

Display of temperature measured in 

room

Bar graph of setpoint offset

Heating active

Cooling active

Alarm: 

Flashing spanner= Alarm switches off the unit

Fixed spanner = Alarm does not switch off the 

unit

Displays the parameter values in % from the 

controller set-up menu

Temperature unit

Delayed comfort mode

Off for Economy/Standby/or 

Frost protection modes,  

depending on set-up

Dehumidification mode

or

Condensate pump fault if flashing

3 manual ventilation   

Automatic position

Special display: 

---: Stop on window contact

Fro:

 Stop on Frost protection device

Cnf:

 KNX Configuration Menu

Add 

x

Controller performing automatic Master/Slave configuration

Lrn:

 Controller in Configuration mode on a KNX bus (Learning mode for ETS)

del:

 Controller performing automatic Master/slave deconfiguratione

Err: 

Error occurred during Master/Slave configuration

3 - MEANING OF SYMBOLS

Symbols

Display version

Dial version

Heating

Heating symbol 

 fixed

Heating LED fixed

Refrigeration

Air conditioning symbol 

 fixed

Air conditioning LED fixed

Delayed comfort

Hourglass 

 + ventilation status

One ventilation LED lit (according to user 

Comfort not delayed

Ventilation only status

Reduced (Standby, eco, frost protection) set via KNX 

or standby button on terminal

Standby symbol 
No ventilation indication

All ventilation LEDs off

Frost protection by window contact

Three dashes "---" in place of temperature

No ventilation indication

All ventilation LEDs off

Standby or eco by presence contact or clock contact

Standby symbol   No ventilation indication

All ventilation LEDs off

Setpoint adjustment

Depends on set-up

Ventilation

1, 2 or 3 ventilation symbols displayed simultaneously 

to indicate LS, MS or HS.

If auto is selected, the AUTO symbol appears in 

addition to the ventilation symbols

If AUTO selected, the LED for current speed is lit.

If AUTO is off, the speed indicator gives the manual 

speed selected.

Dehumidification function

Fixed water drop

Air conditioning LED flashing

Indoor environment sensor fault if indoor environment 

sensor assigned priority

Adjustable spanner fixed

No particular indication

Return sensor fault if return sensor assigned priority

Adjustable spanner fixed

No particular indication

Simultaneous fault on indoor environment and return 

sensors

Adjustable spanner flashing

H air conditioning LEDs flashing simultaneously

Safety sensor fault, “anti-condensation”

Adjustable spanner flashing

H air conditioning LEDs flashing simultaneously

Condensate drain pump alarm

Flashing water drop

H air conditioning LEDs flashing simultaneously

Fan unit motor assembly alarm

Adjustable spanner flashing

H air conditioning LEDs flashing simultaneously

General alarm

Adjustable spanner flashing

H air conditioning LEDs flashing simultaneously

Frost protection alarm in fresh air application 

(antifreeze thermostat)

Letters "Fro" in place of temperature 

H air conditioning LEDs flashing simultaneously

Filter needs replacing

Adjustable spanner fixed

No particular indication

Device designated as Master or Slave (P00 ≠ 0 ) but 

has not yet been configured

Adjustable spanner flashing

H air conditioning LEDs flashing simultaneously

Generally speaking:

Alarm not disabling V3000 operation 

Alarm stopping V3000 operation

Adjustable spanner fixed

Adjustable spanner flashing

No particular indication

H air conditioning LEDs flashing simultaneously

EN

 

 

EN - 3 

EN7515935-00

Summary of Contents for V3000 KNX

Page 1: ...V3000 KNX 03 2017 EN7515935 00 C o n t r o l m a n u a l...

Page 2: ......

Page 3: ...IC 6 6 AIR TEMPERATURE MEASUREMENT 10 7 SPECIFICATIONS OF SENSORS USED BY THE V3000 10 8 WATER TEMPERATURE MEASUREMENT 10 9 CONTROL ALGORITHM 11 10 CONNECTING THE FRAME CONTACT 12 11 FRESH AIR 13 12 M...

Page 4: ...etpoint and also access the set up and diagnostic values Standby button This enables you to change the operating mode comfort standby economy frost protection according to the chosen set up Ventilatio...

Page 5: ...up Ventilation 1 2 or 3 ventilation symbols displayed simultaneously to indicate LS MS or HS If auto is selected the AUTO symbol appears in addition to the ventilation symbols If AUTO selected the LE...

Page 6: ...increments of 0 5 19 0 P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode 5 40 increments of 0 5 26 0 P04 Heating Standby setpoint Setpoint for heating control in Standby mode...

Page 7: ...ically restarted 0 1 2 3 0 P47 Operating mode activated by standby button on user terminal 1 Comfort Frost protection 2 Comfort Eco 3 Comfort Standby 1 2 3 1 P48 Comfort override delay Override to rem...

Page 8: ...of 5 75 P59 Hot water coil nominal capacity Nominal capacity in kW of the hot water coil rounded up to the nearest 100W Used for certain energy consuming applications 0 99 0 resolution of 0 1 100 P60...

Page 9: ...17 Heating heat consumption Calculated heat consumption of heating coil display unit hundred kWh d18 Air conditioning heat consumption Calculated heat consumption of air conditioning coil display unit...

Page 10: ...versa If the controller has just been supplied wait for system initiation 6 mins Check the electrical connection of the valves refer to wiring diagram No heating Check that The hot setpoint T C is gre...

Page 11: ...condensates on the cooling coil This alarm is present as long as there is condensation present on the cooling coil Check the water temperature E15 Slave cut off from master No dialogue between a mast...

Page 12: ...bypass often called a 4 way valve Sensor Changeover operating algorithm If the changeover sensor measures water temperature greater than 7 C adjustable in P27 at ambient temperature the water is deeme...

Page 13: ...P48 24 5 the setpoint overrides are stored in all operating scenarios The current fan speed is not memorized and returns to AUTO Operating mode activated by standby button According to parameter P47 p...

Page 14: ...2 Presence contact comfort Eco local override impossible 3 Presence contact comfort Standby local override impossible 4 Condensate pump alarm fan coil unit switched off and cold valve closed 5 Fan un...

Page 15: ...y mechanism being triggered 11 FRESH AIR Parameters P00 and configuration procedure Diagnostic d01 and d02 The V3000 may perform the master slave function via 3 different ways Master slave by hot cold...

Page 16: ...n to 1 5 mins It is completely finished when the fixed display Add 0 appears d To return to normal display press e If the display Err appears an error has occurred Check The bus wiring Its supply Para...

Page 17: ...ave loop a Start with the slave To switch to configurator mode press buttons for 5 seconds Press for 5 seconds until the display dEL flashes b Go on to the master Perform the same operation as above c...

Page 18: ...elow Switch the radio receiver to configuration mode pressing its button for 3 seconds until the green LED starts flashing more slowly On the remote control Remove the insulation tab on the batteries...

Page 19: ...up to 8 terminal units with a single remote control each terminal unit must be equipped with a radio frequency receiver To configure Set P00 to 0 on all the controllers in the master slave loop defaul...

Page 20: ...a Blank terminal b Wall mounted dial terminal 14 TECHNICAL SPECIFICATIONS EN7515935 00 EN 18...

Page 21: ...c Display terminal d Radio frequency receiver EN EN 19 EN7515935 00...

Page 22: ...the room the connection to the controller is provided by means of flexible wires with a maximum length of 30 m and section 1 mm 2 conductors see terminal 1 and 2 of the regulator It is essential to u...

Page 23: ......

Page 24: ...in mind CIAT reserves the right without notice to proceed with any technical modification Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 i...

Reviews: