Faults
Probable cause
Solution
Cooling fluid
outlet temperature
too high
a) The suction pressure is above the normal
level:
- Controller setpoint incorrect
- Heat load higher than specified
- Water flow rate too high
- Electronic control inoperative
- Power variation system faulty
- Display the correct setpoint
- Check the reports (or install an additional unit if available)
- Adjust the flow rate to the specified value
- Check the operation of the temperature and power controllers
- Check the operation of the compressor control slide
b) The suction pressure is below the normal level:
- Lack of refrigerant
- Incorrect refrigerant supply to evaporator
- Find the leak(s) and top up the charge
- Check the electrical valve, the expansion valve and, if
necessary, the filter dryer fouling level
14. PERMANENT SHUTDOWN
14.1 Decommissioning
Separate the units from their energy sources, allow them to
cool then drain them completely.
14.2 Dismantling recommendations
Use the original lifting equipment.
Sort the components according to their material for recycling
or disposal, in accordance with regulations in force.
Check whether any part of the unit can be recycled for
another purpose.
14.3 Fluids to be recovered for treatment
-
R134a refrigerant
-
Energy transfer fluid: depending on the installation,
water, glycol/water mix...
-
Compressor oil
14.4 Materials to be recovered for recycling
-
Steel
-
Copper
-
Aluminium
-
Plastics
-
Polyurethane foam (insulation)
14.5 Waste Electrical and
Electronic Equipment (WEEE)
At the end of its life, this equipment must be disassembled
and contaminated fluids removed by professionals and
processed via approved channels for electrical and
electronic equipment (WEEE).
-
In France, CIAT has formed a partnership with ECOLOGIC
for the collection and recovery of professional waste
governed by European Directive WEEE 2012/19/EU.
This partnership simplifies the mandatory administrative
procedures and ensures that old equipment is recovered
via an official, structured channel. In terms of renovation
work in France (mainland and overseas), for every CIAT
unit installed, our partner will collect and dismantle
your existing equipment (see conditions with Ecologic).
To request collection, please contact Ecologic:
01 30 57 79 14 -
-
For other countries, please refer to the legislation in
force and the specific solutions available to ensure your
waste is processed legally.
Summary of Contents for POWERCIAT2 LX
Page 1: ...POWERCIAT2 LX LXC AQUACIAT 2 Instruction manual 04 2014 N 13 47 B...
Page 2: ......
Page 39: ...EN EN 37 NA13 47 B...
Page 40: ...NA13 47 B EN 38...
Page 41: ......