EN-89
EREBA He
Par.
CIAT
Jbus
Mnemonic
Description
Range
Default
Unit
WUI
Table
766
jbus_tmt
JBus Comm. Timeout
0 to 600
600
s
RW
RW
JBUSCONF
767
mbusoff1
Modbus Display Offset
0 to 61440
16384
-
RW
RW
JBUSCONF
768
mbusoff2
Modbus Setpoint Offset
0 to 61440
32768
-
RW
RW
JBUSCONF
769
mbusoff3
Modbus Config Offset
0 to 61440
28672
-
RW
RW
JBUSCONF
770
mbusoff4
Modbus Service Offset
0 to 61440
36864
-
RW
RW
JBUSCONF
771
pool_typ
Pool Heating Type
0 to 2
0
-
RW
RW
POOLCONF
772
pool_vlv
Pool 3-way Valve runtime
0 to 240
30
s
RW
RW
POOLCONF
773
pool_vsp
Pump Speed in Pool Heat.
19 to 100
100
%
RW
RW
POOLCONF
774
pool_stp
Pool Heating Setpoint
20 to 35
28
1/10°C
RW
RW
POOLCONF
775
pool_dow
Pool Heating Schedule
00000000 to 11111110
00000000
-
RW
RW
POOLCONF
776
poolstrt
Pool Heating Start Time
00:00 to 23:59
10:00
hh:mm
RW
RW
POOLCONF
777
poolstop
Pool Heating Stop Time
00:00 to 23:59
16:00
hh:mm
RW
RW
POOLCONF
778
pool_time
Pool Exception Time
1 to 24
4
h
RW
RW
POOLCONF
779
pooloatt
Pool Heating OAT Thresld
5 to 30
5
1/10°C
RW
RW
POOLCONF
780
poolewtt
Pool Heating EWT Thresld
5 to 30
10
1/10°C
RW
RW
POOLCONF
781
poolctlp
Pool Heating LWT CtrlPnt
30 to 50
40
1/10°C
RW
RW
POOLCONF
782
Pool Heating Max Runtime
30 to 720
30
min
RW
RW
POOLCONF
(1) Corrected Inverter TO parameter [P039] enables to correct the value measured by TO sensor (located on the air heat exchanger). And OAT [P001] is egal to to2 [P039]
7 - PARAMETERS OVERVIEW