EN-87
EREBA He
Par.
CIAT
Jbus
Mnemonic
Description
Range
Default
Unit
WUI
Table
504
cust_di7
Customized DI#7 Config
-15 to 15
0
-
RW
RW
GEN_CONF
505
cust_di8
Customized DI#8 Config
-15 to 15
0
-
RW
RW
GEN_CONF
500
cust_do5
Customized DO#5 Config
0 to 9
4
-
RW
RW
GEN_CONF
506
Cust_do8
Customized DO#8 Config
0 to 12
1
-
RW
RW
GEN_CONF
507
Cust_do9
Customized DO#9 Config
0 to 12
2
-
RW
RW
GEN_CONF
508
tr_type
Refrigerant Temp Type
0 to 2
0
-
RW
RW
GEN_CONF
509
5080H
ewt_type
EWT Sensor Type
0 to 1
1
-
RW
RW
GEN_CONF
510
iat_type
IAT Sensor Type
0 to 3
0
-
RW
RW
GEN_CONF
511
oat_type
OAT Sensor Type
0 to 3
0
-
RW
RW
GEN_CONF
512
iat_bias
IAT Sensor Bias
-5,0 to 5,0
0,0
1/10 K
RW
RW
GEN_CONF
513
oat_bias
OAT Sensor Bias
-5,0 to 5,0
0,0
1/10 K
RW
RW
GEN_CONF
514
4FE6H
oat_min
Minimum OAT for Heating
-20,0 to 10,0
-20,0
1/10°C
RW
RW
GEN_CONF
515
oat_max
Maximum OAT for Heating
5,0 to 99,0
99
1/10°C
RW
RW
GEN_CONF
516
oat_minc
Minimum OAT for Cooling
0,0 to 40,0
0
1/10°C
RW
RW
GEN_CONF
517
freez_dt
Anti-Freeze Delta Setpoint
0,0 to 6,0
0
°C
RW
RW
GEN_CONF
518
4FD6H
nghtstrt
Night Mode Start Time
00:00 to 23:59
00:00
hh:mm
RW
RW
GEN_CONF
519
4FD8H
nghtstop
Night Mode Stop Time
00:00 to 23:59
00:00
hh:mm
RW
RW
GEN_CONF
520
sparetyp
Spare Sensor Type
0 to 5
0
-
RW
RW
GEN_CONF
521
ui_type
User Interface Type
0 to 3
0
-
RW
RW
UI_CONF
522
ui_accss
Parameter Access from UI
0 to 3
3
-
RW
RW
UI_CONF
523
ui_tmt
Interface Comm. Timeout
0 to 240
60
s
RW
RW
UI_CONF
524
ui_back
Backlight Timeout
0 to 7
2
-
RW
RW
UI_CONF
525
ui_buzz
Buzzer on key press
0/1 [No/Yes]
No
-
RW
RW
UI_CONF
526
timebrod
Interface Time Broadcast
0/1 [No/Yes]
Yes
-
RW
RW
UI_CONF
527
509EH
ser_pass
Service Password
0 to 9999
120
-
RW
RW
UI_CONF
528
5002H
usr_pass
User Password
0 to 9999
0
-
RW
RW
UI_CONF
541
powr_lim
Power Limitation value
50 to 100
75
%
RW
RW
CMP_CONF
542
4FD4H
nght_lim
Nigh Limitation value
50 to 100
75
%
RW
RW
CMP_CONF
543
dhw_lim
DHW Limitation value
50 to 100
100
%
RW
RW
CMP_CONF
544
pool_lim
Pool Heating Limitation
50 to 100
70
%
RW
RW
CMP_CONF
560
flui_typ
Fluid Type
1 to 2
1
-
RW
RW
PMP_CONF
561
pmp_ext
External Main Pump Ctrl
0/1 [No/Yes]
0 [No]
-
RW
RW
PMP_CONF
562
4FF4H
flw_chko
Flow Checked if Pump Off
0/1 [No/Yes]
1 [Yes]
-
RW
RW
PMP_CONF
563
4FEEH
pmp_stck
Anti-sticking function
0/1 [No/Yes]
1 [Yes]
-
RW
RW
PMP_CONF
564
4FF0H
sampling
Pmp Sampling Time Stby
5 to 240
15
min
RW
RW
PMP_CONF
565
pmp_log
Main Pump Logic
1 to 3
1
-
RW
RW
PMP_CONF
566
vsp_log
Var Speed Pump Logic
0 to 1
1
-
RW
RW
PMP_CONF
567
50ACH
vsp_min
Minimum Pump Speed
19 to 100
19
%
RW
RW
PMP_CONF
568
50C0H
vsp_max
Maximum Pump Speed
19 to 100
100
%
RW
RW
PMP_CONF
569
50A4H
dt_stp
Water Delta T Setpoint
2,0 to 20,0
5
1/10 K
RW
RW
PMP_CONF
570
dt_kp
Delta T Proport. Gain
-10,000 to -0,001
-2,000
-
RW
RW
PMP_CONF
571
dt_ti
Delta T Integral Time
10 to 120
20
s
RW
RW
PMP_CONF
572
dt_ts
Delta T Sample Time
10 to 120
10
s
RW
RW
PMP_CONF
573
add_pmp
Additional Pump Logic
0 to 4
0
-
RW
RW
PMP_CONF
581
ht_curv
Heat Clim Curve Select
-1 to 12
-1
-
RW
RW
CLIMCURV
582
9C60H
ht_min_a
Heat Minimum OAT
-30,0 to 10,0
-7,0
1/10°C
RW
RW
CLIMCURV
583
9C62H
ht_max_a
Heat Maximum OAT
10,0 to 30,0
20
1/10°C
RW
RW
CLIMCURV
584
9C64H
ht_min_w
Heat Min Water Setpoint
20,0 to 40,0
20
1/10°C
RW
RW
CLIMCURV
585
9C66H
ht_max_w
Heat Max Water Setpoint
30,0 to 60,0
38
1/10°C
RW
RW
CLIMCURV
586
cl_curv
Cool Clim Curve Select
-1 to 2
-1
-
RW
RW
CLIMCURV
587
9C56H
cl_min_a
Cool Minimum OAT
0,0 to 30,0
20
1/10°C
RW
RW
CLIMCURV
588
9C58H
cl_max_a
Cool Maximum OAT
24,0 to 46,0
35
1/10°C
RW
RW
CLIMCURV
589
9C5AH
cl_min_w
Cool Min Water Setpoint
5,0 to 20,0
10
1/10°C
RW
RW
CLIMCURV
590
9C5CH
cl_max_w
Cool Max Water Setpoint
5,0 to 20,0
18
1/10°C
RW
RW
CLIMCURV
595
dry_stp
Drying Starting Setpoint
20,0 to 40,0
20
1/10°C
RW
RW
DRYING
596
drystep1
Drying Warm-up days
0 to 99
3
-
RW
RW
DRYING
597
drystep2
Drying Ramp-up days
0 to 99
4
-
RW
RW
DRYING
598
drystep3
Drying Hold-up days
0 to 99
4
-
RW
RW
DRYING
599
drying_time
Drying Runtime
N,A,
0
hours
RO
RO
RUNTIME2
601
500CH
bck_type
Backup Type
0 to 10
0
-
RW
RW
BCK_CONF
602
4FFEH
bck_warm
Booster Warm Up Time
0 to 120
30
min
RW
RW
BCK_CONF
7 - PARAMETERS OVERVIEW