CIAT condenciat CD Instruction Manual Download Page 5

EN

 

 

EN - 3 

NA 06.130 C

- Position the unit above the average snow depth in the region where the unit is installed.
- It is strongly recommended to place anti-vibration mounts between the supporting surface and the unit frame and to place 

flexible couplings on the refrigerant pipes to keep vibrations transmitted by solid materials to a minimum (see section on vibration 

dampers).

- Sound level: our units are designed to operate at low noise levels (for this type of equipment).

However, as soon as you begin designing your system, you should take into consideration the outdoor environment to estimate 

the radiated noise and the building type to estimate the noise transmitted through the air and by solid materials (vibrations).

Have an analysis carried out by an acoustical engineer.

Important

: The ambient temperature must not exceed 50°C during the unit's off cycles.

6 - HANDLING AND POSITIONING

To raise the unit, attach the slings to the designated handling holes.
The coordinates of the centre of gravity and the positions of the anchorage points are given on the dimensional drawing.
It is possible to raise the unit with a fork-lift truck provided the necessary precautions are taken to prevent it sliding on the fork-lift 
truck's forks.

Warning: 

- Only attach the slings to the anchorage points intended for this purpose and which are designated on the unit.
- Use slings with a suitable lifting capacity and follow the lifting instructions on the drawings provided with the unit.
- Warning: the centre of gravity is not necessarily in the middle of the unit and the forces applied to the slings are not always 
identical.
- Raise and lower the unit carefully. Take care not to tilt it by more than 15° to avoid any subsequent problems with its operation.
- To avoid damaging the casing, use textile slings with shackles.
- Use a frame with an adjustable centre of gravity to spread the slings away from the top of the unit.

- Always protect the unit casing (panels, uprights, front access door) from damage during handling. Only the frame is designed to 

withstand handling.
- Safety during lifting can be ensured only if all these instructions are followed. Failure to do so may result in damage to the 
equipment and physical injury.

Sizes

A

100 to 150 V

1100

180 to 300 V 

1100

350 to 500 V

2242

540 to 700 V

2242

This drawing is provided for information purposes only. Always refer 
to the pictograms on the unit and in the documentation  
provided with it.

CONDENCIAT CD

Empty weight (kg)

100 V

290

120 V

290

150 V

350

180 V

465

200 V

465

240 V

465

300 V

575

350 V

983

400 V

1082

500 V

1090

540 V

1380

600 V

1499

700 V

1676

2500 min.

Summary of Contents for condenciat CD

Page 1: ...Instruction manual condenciat CD 01 2015 NA 06 130 C...

Page 2: ......

Page 3: ...ION OF REFRIGERATING CIRCUITS AND MAIN COMPONENTS 9 17 TECHNICAL CHARACTERISTICS 10 18 SETTING THE CONTROL AND SAFETY DEVICES 11 19 ELECTRICAL SPECIFICATIONS 11 20 CONDENCIAT CD OPERATING READINGS 12...

Page 4: ...enced and qualified persons may work on such equipment The recommendations and instructions in this manual and on each drawing provided with the unit must be followed In the case of units with pressur...

Page 5: ...on the fork lift truck s forks Warning Only attach the slings to the anchorage points intended for this purpose and which are designated on the unit Use slings with a suitable lifting capacity and fo...

Page 6: ...its A 3 m For information on the dimensions weight anchorage points and centre of gravity refer to the drawings provided with the unit 8 VIBRATION ISOLATORS supplied as standard Anti vibration mounts...

Page 7: ...700 9 FLOOR MOUNTING Top view of FRAME Top view of FRAME Size 100 to 300 V Size 350 to 700 V Hydraulic module Size 180 to 300 CD L1 L2 L3 L4 100 300 316 316 1540 1044 350 500 281 281 2185 2123 540 70...

Page 8: ...iquid pipes 7 8 1 1 8 1 1 8 2 x 1 1 8 11 ELECTRICAL CONNECTIONS The units are designed in accordance with the requirements of European standard EN 60204 1 They comply with the requirements of the mach...

Page 9: ...e circuit in question is shut down Automatic restart once the fault has disappeared and at the end of short cycle protection 14 PRE COMMISSIONING OPERATIONS Note never commission the unit without firs...

Page 10: ...g on the request NOTE 1 Use either of the following to turn off the unit in non emergency situations The switch marked on the wiring diagram A potential free dry contact on the automatic operation con...

Page 11: ...m comp ZPI80 Tandem oil sight glass From comp ZPI80 ADDITION OF GAS RESTRICTION WASHER ON 350 400 MODELS Circuit 2 500 TO 700 ONLY DEHUMIDIFIER FILTER 350 400 models CIRCUIT 2 350 400 models 500 TO 70...

Page 12: ...ower input 2 kW 29 35 42 46 53 61 Low noise version Cooling capacity 1 kW 85 6 93 8 116 120 138 159 Power input 2 kW 30 7 35 5 43 6 47 54 9 62 3 Compressor Type SCROLL Quantity 2 4 Rotation speed rpm...

Page 13: ...ing breaking 25 bar 20 bar 29 bar 23 bar Important safety devices must never be shunted 19 ELECTRICAL SPECIFICATIONS CD 100V 120V 150V 180V 200V 240V 300V 350V 400V 500V 540V 600V 700V Machine protect...

Page 14: ...fore any maintenance Note down the operating readings and perform the checks indicated in the above table at least twice a year and each time a unit is commissioned for seasonal use To prevent acciden...

Page 15: ...stems contain pressurised liquids and vapours All necessary precautions must be taken when opening the system partially A certain amount of refrigerant will be released into the air when the primary r...

Page 16: ...the oil replace it in the corresponding circuit and the dryer If all the oil must be emptied replace it solely with new oil of the same grade as the original oil and stored in a hermetically sealed co...

Page 17: ...ly Set the correct time between two start ups Overload protection disrupted or defective Adjust or replace the overload protection Insufficient power supply voltage Check the electrical wiring if nece...

Page 18: ...the unit terminal block see wiring diagram and connect a C1 contact to them good quality polarity free contact Contact open unit off Contact closed unit authorised to run 25 STAGE CONTROL 1 3 4 5 6 7...

Page 19: ...to 700V 27 CONNECTION PRECAUTIONS Note All inputs Forced stage control Automatic operation control must be polarity free 28 FAN WIRING CONDENCIAT CD 350 to 700 models are equipped with two 2 speed fan...

Page 20: ...ied personnel based on the number of tonnes of CO2 equivalent 5 tCO2eq 50 tCO2eq 500 tCO2eq Test interval Without leak detection system Every 12 months Every 6 months Every 3 months With leak detectio...

Page 21: ...EN EN 19 NA 06 130 C...

Page 22: ...NA06 130 C EN 20...

Page 23: ......

Page 24: ...cations Thermiques Corporation with a capital of 26 728 480 R C S Bourg en Bresse B 545 620 114 With Ecofolio all papers can be recycled This document is not legally binding As part of our continuous...

Reviews: