EN
EN - 11
NA 06.130 C
18 - SETTING THE CONTROL AND SAFETY DEVICES
Control and safety devices
Function
Electrical symbol
Settings
High pressure switch
Manual reset
HP1 (100 to 700)
HP2 (500 to 700)
Tripping: 42 bar ± 0.5
Low pressure switch
Auto reset
BP1 (100 to 700)
BP2 (500 to 700)
Tripping 2.5 bar
120 s. time delay before breaking
Compressor safety
Manual reset
QG1 (100 to 700)
QG2 (100 to 700)
QG3 (540 to 700)
QG4 (540 to 700)
High pressure switch Condensation pressure
control
Auto set
HPR1
HPR2
HPR3 (500 to 700)
HPR4 (500 to 700)
Setting - breaking
25 bar - 20 bar
29 bar - 23 bar
Important: safety devices must never be shunted
19 - ELECTRICAL SPECIFICATIONS
CD
100V
120V
150V 180V 200V
240V
300V
350V
400V 500V 540V 600V 700V
Machine protection rating
IP44
Power supply
3 ph - 50 Hz - 400 V (+10 %/-10 %) + Earth
Monitor circuit voltage
1 ph - 50 Hz - 230 V (+10 %/-10 %) -transformer fitted
Starting current
A
118
137
174
128
139
160
204
255
302
318
250
264
321
Starting current,
SOFT START option
A
55
70
60
70
76
93
90
167
194
210
136
150
233
Breaking capacity (TN-TT
neutral system)
kA
15
10
15
10
35
10
Max. wire cross-section
mm2
10
35
70
50
95
Max. nominal current (1)
A
23.9
25.9
32.9
36.9
44.9
50.5
64.7
74.8
84.6
100.0
114.8
128.8
140.8
(1) Current for selecting the power supply cable