Table of actual flow rates for the DE05UCC pump with Ø 6 mm PVC internal pipe:
TABLE OF ACTUAL FLOW RATES (l/h)
Discharge height
Total pipe length (internal Ø, 6 mm)
5 m
10 m
20 m
30 m
1 m
10,4
9,1
8,3
7,3
2 m
8,5
7,8
7
6,4
3 m
7,9
7,1
6,3
5,8
4 m
7
6
5,3
4,9
Under operating conditions outside the recommended temperature and relative humidity range (page EN-2), the
discharge pipe must be insulated to prevent condensation, which could damage the installation and the pump. We
recommend using a transparent colourless PVC type pipe with internal diameter 6 mm/external diameter 9 mm. It
is essential to ensure that the pump connections are sealed. A clamp can be used for this purpose.
Check the unit selection data to determine the maximum condensate flow rate.
Note: This accessory must always be used with a valve control device, to ensure valve control of the high
safety device when the valve is closed (closure of the condensate drains).
4.6 - Electrical connections
Wiring diagram for connecting several units
Incorrect wiring for several units
Correct wiring for several units
4 - INSTALLATION AND CONNECTIONS
COADIS LINE
TM
600
EN-22
Summary of Contents for COADIS LINE 600
Page 1: ...COADIS LINE TM 600 05 2022 EN7521261 02 Instruction manual...
Page 2: ...35kg 50 C 10 C COADIS LINETM 600 II...
Page 3: ...Fig 1 g h k b j d j e c f a III COADIS LINETM 600...
Page 5: ...Fig 4 Recommended Visual 360 Visual 180 Pr conis 600mm 300 mini a b V COADIS LINETM 600...
Page 6: ...Fig 5 45 a c d b COADIS LINETM 600 VI...
Page 7: ...Fig 6 Fig 7 Fig 8 a a b 131 5 202 67 5 157 40 S1 S E E1 60 18 5 VII COADIS LINETM 600...
Page 10: ...Fig 13 Fig 14 a a b Fig 15 a Fig 16 a b Fig 17 COADIS LINETM 600 X...
Page 11: ...Fig 18 a b c d e f g XI COADIS LINETM 600...
Page 12: ...Fig 19 a b Fig 20 a b Fig 21 COADIS LINETM 600 XII...
Page 31: ......