8 - INSTALLER SETTINGS
N°
Description
Possible choices
24
Cut-off on setpoint:
Makes a stop or not the ventilation setpoint
Unit
-
Allows two modes of operation:
-YES: switching off the fan to obtain the desired
- NO: your installation will be in permanent ventilation (limits the
stratification phenomenon in WINTER, ensures air circulation
ETA) .
Min
-
Max
-
Defaut
Oui
Increment
-
25
Temporisation de la post-
ventilation:
Sets the delay time
Unit
mn
Sets the duration of post - ventilation to the judgment of the
electric battery.
This delay serves to remove all the calories emitted by inertia
after stopping the electric battery.
Min
1
Max
20
Defaut
2
Increment
1
28
Number of electric power stage
controlled:
Unit
-
Sets the number of power stage electric battery to drive:
H4350: 9.6 kW
2 floors
H4400: 18.9 kW
2 floors
H4500: 28.8 kW
2 floors
H4500: 43.2 kW
3 floors
Min
2
Max
3
Defaut
2
Increment
-
29
Number of controlled power box:
Sets the number of slaves controlled by a
master controller:
Unit
-
This parameter defines the number of slave box controlled by a
controller BOX ELEC Eco +
The home setting must match the position of the switches (see
page 5)
Min
1
Max
3
Defaut
1
Increment
-
EN-25
BOX ELEC Eco+
Summary of Contents for BOX ELEC Eco+
Page 1: ...BOX ELEC Eco 08 2019 XX7570605 00 Manuel de r gulation C o n t r o l m a n u a l...
Page 14: ...11 SCHEMA DE RACCORDEMENT BOX ELEC Eco FR 14...
Page 15: ...FR FR 15 BOX ELEC Eco...
Page 28: ...11 WIRING DIAGRAM BOX ELEC Eco EN 28...
Page 29: ...EN EN 29 BOX ELEC Eco...
Page 30: ......
Page 31: ......