7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Reset Configuration Menu – RESETCFG
Name
Status
Default
Unit
Displayed text*
Description
1
cr_sel
0 to 4
0
-
Cooling Reset Select
Cooling reset selection
2
hr_sel
0 to 4
0
-
Heating Reset Select
Heating reset selection
3
0=None, 1=OAT, 2=Delta T 0 = None, 1 = OAT, 2 = Delta T
4
3=4-20mA control
3 = 4-20 mA control
5
4=Space Temp
4 = Space temperature
6
7
Cooling
Cooling
8
oat_crno
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
OAT No Reset Value
OAT, no reset value
9
oat_crfu
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
OAT Full Reset Value
OAT, max. reset value
10
dt_cr_no
0 to 14.0
0 to 25.0
0
0
^C
^F
Delta T No Reset Value
Delta T, no reset value
11
dt_cr_fu
0 to 14.0
0 to 25.0
0
0
^C
^F
Delta T Full Reset Value
Delta T, max. reset value
12
I_cr_no
0 to 20
0
mA
Current No Reset Value
Current, no reset value
13
I_cr_fu
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
14
spacr_no
-9.94 to 52.22
14.0 to 125.0
-10.0
14
°C
°F
Space T No Reset Value
Space temperature, no reset value
15
spacr_fu
-9.94 to 52.22
14.0 to 125.0
-10.0
14
°C
°F
Space T Full Reset Value Space temperature, max. reset value
16
cr_deg
-16.80 to 16.80
-30.0 to 30.0
0
0
^C
^F
Cooling Reset Deg. Value Maximum cooling reset value
17
18
Heating
Heating
19
oat_hrno
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
OAT No Reset Value
OAT, no reset value
20
oat_hrfu
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
OAT Full Reset Value
OAT, max. reset value
21
dt_hr_no
0 to 14.0
0 to 25.0
0
0
^C
^F
Delta T No Reset Value
Delta T, no reset value
22
dt_hr_fu
0 to 14.0
0 to 25.0
0
0
^C
^F
Delta T Full Reset Value
Delta T, max. reset value
23
I_hr_no
0 to 20
0
mA
Current No Reset Value
Current, no reset value
24
I_hr_fu
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
25
spahr_no
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
Space T No Reset Value
Space temperature, no reset value
26
spahr_fu
-9.94 to 52.22
14.0 to 125.0
-10.0
14.0
°C
°F
Space T Full Reset Value Space temperature, max. reset value
27
hr_deg
-16.80 to 16.80
-30.0 to 30.0
0
0
^C
^F
Heating Reset Deg. Value Maximum heating reset value
* Depends on the selected language (French by default).
Backup Configuration Menu – BACKUP
Name
Status
Default
Unit
Displayed text*
Description
1
boil_th
-14.98 to 15.26
5.0 to 59.0
-10.0
14.0
°C
°F
Boiler OAT Threshold
Boiler OAT threshold
2
ehs_th
-4.90 to 21.42
23.0 to 70.0
5.0
41.0
°C
°F
Elec Stage OAT Threshold
Electric heater stage OAT threshold
3
ehs_pull
0 to 60
0
min
Electrical Pulldown Time
Electrical pulldown time
4
ehs_back
no/yes
no
-
Last EHS for backup
Last electric heater stage for backup
5
ehs_defr
no/yes
no
-
Quick EHS for defrost
Quick EHS for defrost
6
ehs_kp
-20 to 20
2
-
EHS Proportional Gain
EHS proportional gain
7
ehs_ki
-5 to 5
0
-
EHS Integral Gain
EHS integral gain
8
ehs_kd
-20 to 20
0
-
EHS Derivative Gain
EHS derivative gain
* Depends on the selected language (French by default).